Lennox Hearth Outdoor Fireplace MP 36OD User Manual

INSTALLATION  
INSTRUCTIONS  
MERIT PLUS® SERIES  
36" Indoor / Outdoor Wood Burning Fireplaces  
P/N 850,030M REV. B 04/2006  
MODEL  
MP-36OD  
This installation manual will enable you to obtain a safe, efficient and de-  
pendableinstallationofyourreplacesystem.Pleasereadandunderstand  
these instructions before beginning your installation.  
Do not alter or modify the fireplace or its components under any circum-  
stances. Any modification or alteration of the fireplace system, including  
but not limited to the fireplace, chimney components and accessories,  
may void the warranty, listings and approvals of this system and could  
result in an unsafe and potentially dangerous installation.  
IMPORTANT! TO ASSURE PROPER ALIGNMENT OF GLASS  
DOORS: INSTALL THIS FIREPLACE IN A SQUARE AND PLUMB  
CONDITION, USING SHIMS AS NECESSARY AT SIDES AND/OR  
BOTTOM.  
RETAIN THESE INSTRUCTIONS  
FOR FUTURE REFERENCE  
VEUILLEZ GARDER CE MANUEL  
POUR RÉFÉRENCE FUTURE.  
NOTE: This fireplace has been listed and approved for use outdoors or  
indoors.  
A French manual is available upon request. Order P/N 850,030CF  
CAUTION! THIS FIREPLACE IS EQUIPPED TO BE READILY IN-  
STALLED OUTDOORS. IF INSTALLED INDOORS, YOU MUST  
INSTALL THE COMBUSTION AIR COVER PROVIDED WITH THE  
INSTALLATION KIT OR PURCHASE THE OPTIONAL OUTSIDE AIR  
KIT GATE OAKG-OD. SEE INSTRUCTIONS INSIDE THIS MANUAL  
FOR FURTHER DETAILS.  
Ce manuel d’installation est disponible en francais, simplement en  
faire la demande. Numéro de la pièce 850,030CF.  
IMPORTANT! POUR ASSURER L’ALIGNEMENT APPROPRIÉ DES  
PORTES DE VERRE : INSTALLEZ CE FOYER SUR UNE SURFACE  
PLANE ET METTRE À NIVEAU EN UTILISANT DES CALES AU  
BESOIN SUR LES CÔTÉS OU EN DESSOUS.  
ATTENTION! CETTE CHEMINÉE A ÉTÉ ÉNUMÉRÉE ET APPROU-  
VÉE POUR ÊTRE AISÉMENT INSTALLÉE À L’INTÉRIEUR OU  
DEHORS. S’INSTALLÉÀLINTÉRIEUR, VOUSDEVEZINSTALLER  
LA COUVERTURE D’AIR DE COMBUSTION ÉQUIPÉE DE KIT  
D’INSTALLATION OU ACHETER LA PORTE EXTÉRIEURE FAC-  
ULTATIVE OAKG-OD DE KIT D’AIR. VOIR LES INSTRUCTIONS À  
LINTÉRIEUR DE CE MANUEL POUR D’AUTRES DÉTAILS.  
OTL Report No.  
116-F-35-2  
 
Note: These fireplace systems are not difficult  
to install. However, in the interest of safety, it is  
recommendedthattheinstallerbeaqualifiedor  
certified “tradesman” familiar with commonly  
accepted fireplace installation and safety tech-  
niques as well as prevailing local codes.  
Vinyl siding is not recommended for use  
on the front of the fireplace due to the heat  
the unit produces. This can cause the vinyl  
siding to deteriorate.  
WARNING  
If insulation is used, the fireplace  
mustnotbeplaceddirectlyagainst  
it. Insulation or vapor barriers, if  
used, must first be covered with  
gypsum board, plywood, particle  
board or other material to assure  
insulation and vapor barriers  
remain in place.  
Note: Illustrations shown reflect “typical”  
installations with nominal dimensions and  
are for design and framing reference only.  
Actual installations may vary due to individual  
design preferences. However, always maintain  
minimum clearances to combustible materials  
and do not violate any specific installation  
requirements.  
INTRODUCTION  
General Information  
These fireplaces are traditional radiant heat  
fireplaces with standard bar grates, optional  
Outside Air Kits (required for outdoor installa-  
tions) and optional Operable Bi-Fold Stainless  
Outdoor Glass Doors and Weather Cover.  
These fireplaces have been tested and listed  
by OMNI-Test Laboratories, Inc. (Report No.  
116-F-35-2) to U.L. 127 (USA) and U.L.C.  
S610 (Canada). These units are intended for  
indoor and outdoor installations as specified  
in this manual.  
AVERTISSEMENT  
These appliances are approved for installation  
indoors or outdoors.  
Indoors: These appliances are approved  
for installation in residential homes and  
otherbuildingsofconventionalconstruction  
including commercial, not in manufactured  
homes(see Figure 5).  
Si un isolant est utilisé, il ne doit  
pasvenirencontactaveclefoyer.  
Lisolant ou le coupe vapeurs, si  
utilisée, doit d’abord être couvert  
d’un panneau de gypse, contre-  
plaqué, panneaudeparticulesou  
d’unautrematérielpours’assurer  
que l’isolant et le coupe vapeurs  
demeurent en place.  
ForinstallationsinCanada,thechimneyclear-  
ance to combustibles must be 2 inches and  
the Cold Climate Kit must be installed.  
Outdoors: Theseappliancesareapprovedfor  
installion against an outside wall of a house,  
or as a freestanding fireplace on the porch,  
patio, or located in the yard (see Figure 6).  
The Outdoor Fireplace must be enclosed to  
prevent impact damage to the outside of the  
fireplace. Build an outside enclosure out of  
standard building materials, being careful to  
maintain the minimum air clearances speci-  
fied in these Installation Instructions. When  
installing the fireplace as a freestanding unit  
onyourporch,patioorbackyard,itmustalso  
beenclosedtopreventimpactdamagetothe  
fireplace. However, the enclosure must now  
be finished on all four (4) sides. The exterior  
oftheenclosuremaybenishedinatextured  
plywood, a wood clapboard siding, brick, or  
a cultured stone.  
WARNING  
Do not pack or fill required air  
spaces with insulation or other  
material.Nomaterialisallowed  
in these areas.  
These fireplace systems are designed for in-  
stallation in accordance with the National Fire  
Protection Standard for chimneys, fireplaces  
and solid fuel burning appliances; NFPA 211-  
latest edition and in accordance with codes  
such as the BOCA Basic/National Codes, the  
Standard Mechanical Code and the Uniform  
Building Codes.  
AVERTISSEMENT  
Ne remplissez pas les espaces  
libres d’une matière isolante ou  
de tout autre type de matériel.  
Aucun matériel n’est permis  
dans ces espaces vides.  
TYPICAL INSTALLATION - INDOORS  
Chimney and  
Termination  
TYPICAL INSTALLATION - OUTDOORS  
Termination (FTF8-CTD/CTDT)  
Storm Collar  
(FSC)  
Outdoor fireplace  
system less than 15  
feet height must be a  
Flashing  
(Locally  
Outside Air Kit installa-  
tion is optional unless  
mandated by local build-  
ing codes.  
minimum of 10 feet  
Fabricated)  
Chimney Section  
(FTF8-48)  
away from a building or  
combustible structure.  
If installed closer than  
10 feet, the 10 Foot  
Rule applies (see Ten  
Foot Rule Summary on  
Page 15).  
* Outside Air Kit (provided)  
must be installed in  
outdoor installation.  
Outside  
Combustion  
Air Kit  
Use Only Non-Combustible Materi-  
als From Top Of Spacers Down And  
Within 1/2" Min. To Side Frame.  
(Optional)  
7' 3" Min. (using one 4' section)  
Side Frame  
Notes:  
• Framing is shown as  
reference only. It can differ  
according to design and  
local building codes.  
• Fireplace is shown for  
illustration purposes only.  
It may differ from actual  
model.  
*Air Inlet  
(Provided)  
Metal Safety Strips  
And Hearth Extension  
Required When Installed  
On Combustible Floor  
Or In Proximity To  
Note: Framing and fireplace shown as reference  
only. It can differ according to design and local  
building codes.  
Combustible  
Floor/Covering.  
Figure 2  
Figure 1  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
3
 
INDOOR INSTALLATIONS - The minimum  
installed height of the completed fireplace  
system for is 15' 0." The maximum height is  
60' 0" (see Table 1).  
OUTDOOR INSTALLATIONS  
Minimum System Height  
Security's FTF8 Pipe  
WARNING  
Failure to use manufacture  
provided parts, variations in  
techniques and construction  
materialsorpracticesotherthan  
those described in this manual  
maycreatearehazardandvoid  
the limited warranty.  
Vertical Installation  
7' 3"  
15' 0"  
25' 0"  
OUTDOOR INSTALLATIONS - The minimum  
installed height of the completed fireplace  
system is 7' 3." The maximum height is 60"  
(see Table 2).  
One Offsets  
Two Offsets  
Table 2 - See following Notes  
The fireplace and chimney system must be  
enclosed when installed in or passing through  
alivingareawherecombustiblesorpeoplemay  
comeincontactwithit.Thisisimportanttopre-  
vent possible personal injury or fire hazard.  
Notes (Table 2)  
• Outdoor fireplace system less than 15 feet  
height must be a minimum of 10 feet away  
from a building or combustible structure.  
The 10 foot rule applies on all cases (see  
ten foot rule summary on Page 15).  
AVERTISSEMENT  
Léchec d’utiliser la fabrication  
les parties fournies, les varia-  
tions dans les techniques et le  
matériel de construction ou les  
pratiques autre que ceux-là ont  
décritdanscemanuelpeutcréer  
un risque d’incendie et un vide  
la garantie limitée.  
The system height may be reduced to a  
singlelengthofFTF8-48pipeandtermination  
with either the FTF8-CTD or FTF8-CTDT for  
a minimum height on a complete system of  
7' 3." The fireplace must be installed as a  
Freestandingsystemandlocatedaminimum  
of 10' away from any building or structure  
(refer to Figure 1).  
For questions, please call your distributor or  
the manufacturer. Special restrictions apply to  
the front and facing of the fireplace and nearby  
walls (See Pages 20, 21 & 22).  
CHIMNEY SYSTEM  
The minimum height will vary when using  
other Firecraft or Lennox Terminations.  
Thesereplacesaredesignedandcodelistedfor  
usewithSecurityChimneysFTF8chimneySys-  
tem only. Always use Security Chimneys FTF8  
chimney components with these fireplaces. Do  
not modify or alter these components as this  
may cause a potential serious hazard and void  
the Warranty.  
Whencompletethesereplacesystemsconsists  
of five basic “sub-systems”:  
1. The Fireplace  
2. The Chimney and Termination  
3. The Optional Glass Doors  
4. The Optional Outside Air Kits  
5. The Optional Weather Cover (for outdoor  
installations)  
Chase Enclosure  
A chase is a vertical box-like structure con-  
structedtosurroundthereplaceandchimney.  
Refer to Figure 4 for a typical chase configura-  
tion. As with all chimney installations, avoid  
overhead obstructions such as trees, power  
lines, etc. A chase should be constructed and  
insulated just like any outside wall. In a cold  
climate, we recommend the base of the chase  
should also be insulated between the solid  
continuous floor beneath the fireplace and the  
chasebottom.Chaseinsulationinacoldclimate  
installation is not required for safety.  
Chimney Height - Indoor Installations  
The total height of your completed fireplace  
system from the surface the fireplace rests on  
to the chimney top must not exceed 60' and  
mustalsomeetminimumheightrequirements.  
Refer to the minimum system height chart (see  
Table 1).  
CLEARANCES AND HEIGHT  
REQUIREMENTS  
The fireplace may be placed on or near normal  
construction materials*. The outside air kit,  
firestop spacer and roof flashing (not chase  
flashings) may be placed directly on or against  
normal construction materials. **  
Note: Do not insulate the chase cavity with  
blown or fill type insulation materials.  
Chimney Height - Outdoor Installations  
The total height of your completed fireplace  
system from the surface the fireplace rests on  
to the chimney top must not exceed 60' and  
mustalsomeetminimumheightrequirements.  
Refer to the minimum system height chart (see  
Table 2).  
Note:Localcodesmaynotrequirerestopping  
at the ceiling levels for outside chase installa-  
tions. However, it is recommended for safety  
and the reduction of heat loss.  
A combustible mantel may be installed 12"  
above the opening of the fireplace as per NFPA  
211-latest edition. In Canada, the minimum is  
18" above the fireplace opening.  
ASSEMBLY OUTLINE  
Before You Start  
* In the USA, the chimney and fireplace outer  
wrapper require a minimum 1" air space  
to insulation and construction materials.  
Check your inventory list to be sure you have  
all the necessary parts supplied in good us-  
able condition. Check also for any concealed  
damage.  
INDOOR INSTALLATIONS  
Minimum System Height  
Security's FTF8 Pipe  
InCanada,thechimneyandreplaceouter  
wrapper require a minimum 2" air space to  
insulation and construction materials.  
Checktheoperationofthedamper. Thedamper  
is controlled through the use of a control lever  
located within the firebox opening at the top  
center in front of the firebox lintel (Figure 3).  
The control lever snaps into place at either  
extreme of its range of motion. When locked  
in position all the way to the right, the damper  
is open. When locked in position all the way to  
the left, the damper is closed.  
Vertical Installation  
One Offsets  
15' 0"  
15' 0"  
25' 0"  
** Construction Materials:  
Two Offsets  
• Framing Materials • Paneling  
• Particle Board  
• Dry Wall  
• Flooring  
• Plywood  
Table 1  
• Noncombustible Insulating Materials  
• Etc.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
4
 
Whenchoosingalocation,caremustbetaken  
to avoid places where flooding or running  
water may be a problem.  
Indoor Locations - Carefully consider the  
position of the fireplace opening with re-  
spect to the location of adjacent or nearby  
stairwells, bath or kitchen exhaust fans  
and/or return air registers for forced air  
furnaces/air conditioners that could cause  
a smoking fireplace condition if the house  
is tightly insulated.  
DO NOT place furniture or other items such  
as plants or decorative objects within 60” of  
the fireplace front face.  
Damper  
Open  
Damper  
Closed  
Lintel  
Combustion Air Actuator  
(when installed)  
Outdoor Locations - Top View  
LIVING SPACE  
Indoor Locations - Top View  
Figure 3  
Chase Enclosure - Indoor Installation  
Air Inlet (inlet  
Insulate Joists  
Same As Ceiling  
must be free of  
Optional  
any obstructions)  
Hearth  
Hearth  
Extension  
PATIO  
Hearth  
Draft Stops  
Firestop  
Figure 6  
Optional  
Figure 5  
Outside Chase  
Restrictions for Outdoor installations:  
Outside Air Kit must be installed and  
fully open on the outdoor installation. On  
the indoor installation is optional unless  
mandated by local building codes.  
• Minimum chimney height for the outdoor in-  
stallation is 7' 3" (one 4 foot pipe section).  
• Only non-combustible materials are al-  
lowed on the front face (Front Fireplace  
Frame) and around the perimeter within  
1-5/8” on the top and 1/2" on the sides  
(see Figures 1, 51 & 52).  
CTDT  
Termination  
CAUTION  
To ensure that the outside air  
kit remains open for an outdoor  
installation,thisreplaceshould  
not have a combustion air gate  
control installed (OAKG-OD). If  
this unit is installed indoors,  
you must install the outside  
combustionaircoverprovidedor  
an optional outside air kit gate  
(OAKG-OD) before the fireplace  
is framed in place.  
Note: Non-  
Combustible  
Chase  
Flashing  
Must Be  
Used To  
Cover  
Chase  
Opening  
Combustible materials may project beyond the  
sides of the fireplace opening as long as they  
are kept within the shaded areas illustrated in  
Figure 7.  
Optional  
Insulation  
In Outside  
Walls Of  
Chase  
CLEARANCES  
8'  
Level  
Minimum clearance to combustibles for the  
appliance is as follows: sides and back - 1” (25  
mm), floor-0(0mm), adjacentwall-12(305  
mm), ceiling - 37 1/2” (953 mm).  
Solid  
ATTENTION  
Continuous  
Surface  
Assurer que les restes extérieurs  
dekitd’airouvertspouruneinstal-  
lationextérieure,cettecheminée  
n’ontpasunecommandedeporte  
d’air de combustion a installé  
(OAKG-OD). Si cette unité est  
installéeàl’intérieur, vousdevez  
installer la couverture extérieure  
d’air de combustion fournie ou  
une porte extérieure facultative  
de kit d’air (OAKG-OD) avant  
que la cheminée soit encadrée  
en place.  
Note: Clearance at the nailing tab is 0" (0mm)  
Outside  
Base  
Insulation  
(see Figure 25).  
(Thermal Barrier)  
Figure 4  
Note: Adjacent wall considerations are for  
an adjacent wall on only a single side. Walls  
should not be placed at minimum distance at  
both sides of the fireplace.  
LOCATION OF FIREPLACE  
Carefully select the proper location for heat  
circulation, aesthetics, chimney obstructions,  
air inlet location and clearance to side wall(s).  
With proper pre-planning, a slight adjustment  
of a few inches can save considerable time and  
expenselaterduringconstructionandassembly.  
See Figures 5 & 6 for examples.  
When locating the fireplace, consideration  
must be given to combustibles and final  
finishing. See Figure 5 and confine the final  
location of combustible finish materials to  
the "Safe Zone."  
Frame Surface Not to Be Covered  
With Combustible Materials  
Wall  
Covering  
12"  
45°  
1"  
Door  
Opening  
Outdoor Locations - Carefully consider the  
positionofthereplaceopeningwithrespect  
to the location of adjacent or nearby stair-  
wells, doors, windows, walk ways and over  
hanging trees, patios and wires.  
Safe  
Zone  
12"  
Figure 7 Clearances  
DONOTpermanentlyplacefurnitureorother  
items such as decorative pillows within 60"  
of the fireplace front face.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
5
 
If you plan to raise the fireplace and hearth  
extension, build the platform assembly then  
position fireplace and hearth extension on  
top. Secure the platform to the floor to prevent  
possible shifting.  
ASSEMBLY STEPS  
Outside Air Collar  
Note: The following steps represent the normal  
sequence of installation. Each installation is  
unique, however, and might require a different  
sequence.  
Right Side  
Outside Panel  
on Fireplace  
WATERPROOFING THE FIREPLACE  
Outdoor Installations  
1. Position firebox prior to framing or into  
prepared framing.  
2. (Outdoor Installations) Waterproof the  
fireplace. See Waterproofing The Fireplace  
on Page 6.  
Although the fireplace is designed to drain to  
the front most of the water from rain and other  
sourcesthatmayentertheheartharea,conden-  
sationandunusualconditionsmaycausewater  
to collect inside the fireplace bottom.  
Four (4) Screws  
A
B
3. Install the chimney system.  
4. Installanoutsideaircoveroranairgatekit, if  
fireplace is being installed indoors (optional  
accessory, see Page 23 for ordering infor-  
mation). The Airgate kit is required on all  
INDOOR installations when an outside air  
kit is installed. The Airgate Kit is NOT ap-  
proved for use on outdoor installations.  
5. Install outside air kit (provided). This kit  
is required on ALL outdoor installations  
(optional for indoor installations).  
6. Plumb gas line if a decorative gas appliance  
will be used. (Gas connections should only  
be performed by an experienced, licensed/  
certified tradesman).  
Right Outside  
Panel on  
Fireplace  
To prevent water collection, the builder must  
provide a means to drain water from under  
the fireplace by building or installing a water  
collector of the builder's choice before posi-  
tioning the fireplace on its location.  
Outside air collar Removed  
INDOOR INSTALLATIONS ONLY  
Outside Air Cover  
If the optional outside air kit is not required  
in an indoor installlation, you must install the  
outside air cover to close the opening for the  
outside air kit (see Figure 8, Photo C).  
Outside Air Cover Installed  
Right Side  
7. Complete the installation, finish wall mate-  
rial, surround and hearth extension to your  
individual taste.  
8. Assemble and attach optional glass door  
assembly.  
Outside Panel  
on Fireplace  
Studytheillustrationoftheinstallation,Figures  
1 & 2, to get a general idea of each element of  
your fireplace system.  
WARNING  
Required on indoor installations if  
C
an outside air kit is NOT installed.  
IndoorInstallations-Iftheoptional  
outside air kit is not required, the  
outsideaircovermustbeinstalled  
for safe fireplace operation.  
Viewed from right side of fireplace  
Figure 8  
PRE-INSTALLATION NOTES  
The fireplace may be installed directly on a  
combustible floor or raised on a platform of an  
appropriate height. Do not place fireplace on car-  
peting, vinyl or other soft floor coverings. It may,  
however,beplacedonatwood,plywood,particle  
board or other hard surfaces. Be sure fireplace  
rests on a solid continuous floor or platform with  
appropriate framing for support (and for indoor  
installation ensure that no cold air can enter the  
room from under the fireplace).  
Outside Air Kit Gate Installation  
(optional kit) Indoor Installations Only  
AVERTISSEMENT  
TheinstallationoftheAirGate(shutter)isrequired  
on all indoor installations to prevent cold air  
infiltration when an outside air kit, OAK-OD (duct  
& hood), is installed. The Outside Air Kit Gate,  
OAKG-OD (air gate & arm), must be purchased  
and installed before the fireplace is installed.  
Installations d’intérieur - si le kit  
extérieur facultatif d’air n’est pas  
exigé, la couverture extérieure  
d’air est exigent pour l’opération  
sûre de cheminée.  
The fireplace may be positioned and then the  
framing built around it, or the framing may be  
constructed and the fireplace positioned into  
the opening.  
1. Remove the Outside Air Collar located on  
the right hand side of the fireplace (retain  
the screws). See Figure 8, Photos A & B.  
The Outside Air Cover is included in the Instal-  
lation Instrctuions package provided with this  
fireplace. Follow the steps below:  
Usually, no special floor support is needed for  
the fireplace, however, to be certain:  
2. Install the Outside Air Kit Gate (OAKG-  
OD) per the instructions in the kit and the  
following instructions using the screws  
provided.  
a. Remove the Outside air collar located on  
the side of the fireplace. Do not discrd the  
screws (see Figure 8, Photos A & B).  
1. Estimate the total weight of the fireplace  
system including chimney and surround  
materials such as brick, stone, etc., to be  
installed. Shipping weight for the fireplace  
may be found on Page 9 (see Product  
Reference Information).  
2. Measurethesquarefootageoftheoorspace  
tobeoccupiedbythesystem,surroundsand  
hearth extensions.  
a. Assemble the Air Gate Arm to the Air  
Gate as shown in Figure 9.  
b. With the screws previously removed, install  
the cover provided with the installation  
instructions kit (see Figure 8, Photo C).  
b. Take the Air Gate Assembly and feed the  
arm through the round opening (see Figure  
10)andthenthroughthesideframeopening  
in the front as shown in Figure 11.  
3. Note the floor construction, i.e. 2 x 6’s, 2 x  
8’s or 2 x 10’s, single or double joists, type  
and thickness of floor boards.  
4. Use this information and consult your local  
building code to determine if you need ad-  
ditional support.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
6
 
4. InstallanOutsideAirKit (withductandhood)  
Assemble the Air Gate and Arm as shown.  
Air Gate Assembly  
per the instructions provided with kit.  
Using a screwdriver bend this tab outward, if  
necessary, for the arm to clear the opening  
a. If the outside air kit is NOT installed, you  
must install the Outside Air Cover provided  
with the instructions kit.  
b.IfanoutsideairkitISinstalled,theOutside  
Air Kit Gate must be installed (see Page 23  
of ordering information).  
The Outside Air Kit Gates are required  
on all indoor installations only. They  
are not approved for use on oudoor  
installations.  
Air Gate Arm  
Air Gate Assembly  
Air Gate Operation Instructions  
Firebox  
Arm  
Front Face  
Install the Air Gate Kit per the instructions  
provided with kit (see Page 23 for ordering  
information).  
Side Frame  
Opening  
Air Gate Arm  
Air Gate Kit (purchased separately)  
Feed The Arm Through Side Frame Opening  
Combustion Air Actuator  
When assembled onto appliance, the  
notch here must be positioned as shown  
Figure 11 - Air Gate Arm in Front  
Figure 9- Outside Air Kit Gate  
IMPORTANT! IF THE AIR GATE IS INSTALLED  
UPSIDE DOWN (WITH THE NOTCH POSI-  
TIONED ON THE UPPER HALF) IT WILL NOT  
WORK PROPERLY. REFER TO FIGURE 9.  
c. Ensure the air gate arm remains attached  
to the air gate, secure the Air Gate to the  
fireplace,withthescrewsprovided,asshown  
in Figures 12 & 13.  
Align Air Gate Assembly to Opening  
Figure 12 - Position Air Gate  
Pull Forward to Open,  
Push Back to Close  
d.Verifythemechanismisworkingbypulling  
to open and pushing to close.  
Figure 15  
3. Install the Outside Air Collar with the screws  
To operate, push the end of the actuator arm  
to the left as shown in Figure 15, until it "pops"  
free of its "locked" position. Pull the actuator  
forward to open the combustion air door, and  
push it back to close. To "lock" the combustion  
air door closed, ensure the actuator is pushed  
all the way back then push the end of the actua-  
tors to the right until the step in the actuator  
moves behind the appliance front face within  
the slotted opening.  
removed earlier (see Figure 14).  
Right Outside Panel  
on Fireplace  
Secure Air Gate Assembly 4 Places  
Figure 13 - Install Screws  
Operate the actuator through several cycles  
including the "lock" position. Ensuring proper  
operation and freedom of movement. Return  
the actuator arm to the locked position.  
Reinstall Outside Air Collar  
Position the Air Gate Assembly as Shown  
Figure 10 - Air Gate Assembly to Fireplace  
Figure 14 - Reinstall Connector  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
7
 
Install as follows:  
Note: Secure the duct hood to a vertical post  
withtheinletpositioneddownward.Ensurethat  
nothing blocks the hood opening. This duct  
must never terminate higher than 3 feet below  
the fireplace termination (Figure 17).  
Outside Air Kit Installation (provided)  
Connect the 4" (102 mm) Class 0 air duct  
provided, to the collar on the fireplace with the  
clamps provided in the kit’s hardware package  
(Figure 16).  
These appliances are equipped with a com-  
bustion air inlet collar so that it is possible to  
duct combustion air from the outdoors to the  
firebox. To accomplish an outside air hook-  
up, use only the Outside Air Kit provided with  
these appliances. These kits come complete  
with all components necessary in completing  
a combustion air vent system.  
Route the Class 0 metallic air duct out the back  
wall or side wall, up through the ceiling or floor  
joists to an outside wall. The air duct’s inlet  
should be located above any anticipated  
snow level. Check local building codes for any  
restrictions. We recommend that the inlet be  
at least 4 feet above grade level.  
Indoor Installations - An Air Gate Kit must be  
installed prior to the installation of the Outside  
Air Kit (purchased separately - see Page 23 for  
ordering information).  
3 Feet  
Note: Air inlet ducts must not terminate in  
attic space.  
OutdoorInstallations-Unitsinstalledoutdoors  
are required to have the Outside Air Kit (pro-  
vided) installed without the Air Gate Kit. The  
optionalAirGateKitisnotapprovedonoutdoor  
installations.  
CAUTION  
Air Inlet  
(duct hood)  
Avoid installing the air inlet  
where the opening could be  
blocked by snow, bushes or  
other obstacles. The maximum  
height for the outside air is 50  
feet above the hearth, provid-  
ing the air inlet is terminated a  
minimum of three (3) feet below  
the chimney cap level.  
Figure 17  
Outside Air Kit (provided)  
Duct Hole Framing:  
Required on all Outdoor installations  
Optional on Indoor installations  
Cut or frame a hole through the outside of  
the enclosure for the installation of the duct  
inlet hood. A 5" (127 mm) diameter hole is  
required. Feed the loose end of the flexible  
duct through the hole cut for the inlet hood and  
attach to the collar on the inlet hood using two  
(2) screws. Insert the hood into the opening.  
Secure in place with nails driven through the  
holesinhoodange.Sealwithnoncombustible  
waterproof silicon type caulking. If additional  
duct is needed, use Class 0 metallic air duct  
(refer to Figure 16).  
Air Duct  
Air Inlet  
ATTENTION  
Évitezd’installerlaprised’airou  
l’ouverturepourraitetrebloquee  
par la neige, les buissons ou  
d’autres obstacles. La hauteur  
maximum pour la prise d’air est  
de50pi.Audessusdelabasedu  
foyeràconditionqu’ellesesitue  
à au moins 3 pi. En dessous de  
la sortie de la cheminée.  
Clamps  
Note: Air Inlet  
Must Be Free Of  
Any Obstructions  
Figure 16  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
8
 
FIREPLACE SPECIFICATIONS - MODEL MP-36OD  
OAK-OD Combustion  
Air Kit  
Product Reference Information  
Back Wall of Chase/Enclosure  
Including Finishing Materials, if any.  
Cat.  
No.  
Model  
Ship.  
Weight  
Ship.  
Volume  
H1933 MP-36OD  
175 lb.  
17.3 cu. ft.  
(See Note **)  
G
Framing Dimensions  
K
Header  
A
B1  
B2  
C
41-1/2"  
37-1/2"  
54-1/2"  
28-3/4"  
15-3/8"  
70"  
1054 mm  
A
Rough  
Framing Face  
953 mm  
1384 mm  
730 mm  
391 mm  
1778 mm  
889 mm  
524 mm  
499 mm  
1257 mm  
203 mm  
Inside Chase  
(Unfinished Shown)  
Outside Chase - Indoor Installations  
B1  
B2  
**Note:WhenFramingWith6StudsHeaderMustBe17”  
(432mm)Higher. UseSecurityChimney’sOR15Offset/Re-  
turn Elbow To Recess The Chimney Back 2 1/2” (64mm).  
Flat Frame Down To A False Header At (B1). Maintain  
Required Clearance To Chimney At All Times.  
D
E
A
F
35"  
Fireplace Framing  
G
H
J
20-5/8"  
19-5/8"  
49-1/2"  
8"  
* 1" Air Space to insulation and construction materials on the  
back and sides.  
Back Wall of Chase/Enclosure  
Including Finishing  
Optional  
Outside  
Drainage  
Line  
Air Kit  
Materials if any  
K
Including Finising Materials  
if any  
Combustion  
Air Kit - Optional  
C
A
*
Notes  
G
Due to Lennox' ongoing commitment to quality,  
all specifications, ratings and dimensions are  
subject to change without notice.  
G
H
A
All framing dimensions calculated for 1/2"  
dry wall at the fireplace face. If sheathing the  
chase or finishing with other thickness materi-  
als, calculations will need to be made.  
Rough Framing Face  
(Unfinished Shown)  
Outside Chase  
Rough  
See Page 10 for Ceiling and Roof Framing  
Framing Face  
(Unfinished Shown)  
Outside Chase  
Dimensions  
Back Wall of  
Chase/Enclosure  
Including Finising  
Materials  
Diagrams & Illustrations Not to Scale  
27-1/4”  
OAK-OD Combustion  
Air Kit  
(692 mm)  
if any  
7-13/16  
(198 mm)  
20-1/4”  
D
(514 mm)  
J
F
Appliance  
Top Spacer  
12-1/2"  
OTL Report No. 116-F-35-2  
(318 mm)  
A
40"  
1-1/4"  
E
(1016 mm)  
(32 mm)  
Rough  
42-1/2"  
(1080 mm)  
Framing Face  
(Unfinished Shown)  
Corner Installation  
Top View  
Appliance Top Spacer  
9-5/8”  
(244 mm)  
7-1/2”  
(191 mm)  
9-7/8”  
(251 mm)  
Combustion  
Air Inlet  
36"  
(914 mm)  
37"  
(940 mm)  
Gas Line  
Access  
32"  
(813 mm)  
20-3/16”  
(513 mm)  
Gas Line  
Access  
37"  
(940 mm)  
27-7/8”  
(708 mm)  
2"  
(51 mm)  
9-3/16”  
9-1/16  
17-3/8”  
(233 mm)  
(230 mm)  
(441 mm)  
7-3/16”  
(183 mm)  
12-7/8”  
(327 mm)  
40"  
Junction  
Box  
20-1/4”  
(514 mm)  
(1016 mm)  
42-1/2"  
(1080 mm)  
Figure 18  
Right Side  
Left Side  
Front  
9
 
INSTALLING THE FIREPLACE  
Step 1. Slide the fireplace into prepared fram-  
ing or position fireplace in its final position  
and frame later.  
Framing Ceiling  
Frame the opening for the ceiling as speci-  
ficed here.  
The fireplace may not be recessed into a  
combustible floor. Maintain the floor to hearth  
clearance established by the fireplace lower  
front face.  
B
Note: Faming Dimensions in Canada & USA are different  
because installations in USA require 1" Clearance to pipe.  
Installations in Canada require 2" Clearance to pipe.  
A
Step 2. Insert the provided metal safety strips,  
beneaththereplaceasillustrated(Figures21,  
22 & 23). The safety strips should overlap 1/2  
min. for continual coverage of the floor.  
Ceiling Framing  
Framing Dimensions for Ceiling  
Inches (millimeters)  
Note: Safety strips are not required when fire-  
place rests on a noncombustible surface.  
Flue Type  
A
B
FTF8 Vertical  
(USA)  
14 1/2"  
(368 mm)  
14 1/2"  
(368 mm)  
FTF8 Vertical at 2"  
(Canada)  
16 1/2"  
(419 mm)  
16 1/2"  
(419 mm)  
Top Spacer  
Maintain  
1" (25 mm)  
Air Space  
At Back  
FTF8 Offset 30°  
(USA)  
14 1/2"  
(368 mm)  
25"  
(635 mm)  
FTF8 Offset 30° at 2"  
16 1/2"  
27"  
And Sides  
(Canada)  
(419 mm)  
(686 mm)  
Figure 19  
Hearth  
Extension  
1" (25 mm) Space  
Framing Roof  
Metal Safety Strip  
Floor  
Frame the opening for the roof as  
specificed here.  
Note: Hearth extensions must not interfere with  
circulating grillwork  
Figure 21  
C
Note: Faming Dimensions in Canada & USA are different  
because installations in USA require 1" Clearance to pipe.  
Installations in Canada require 2" Clearance to pipe.  
Maintain  
1" (25 mm)  
Air Space  
At Back  
D
Roof Framing  
And Sides  
Framing Dimensions for Roof  
Inches (millimeters)  
FTF8 at 1" (USA)  
FTF8 at 2" (Canada)  
Hearth  
Pitch  
0/12  
C
D*  
C
D*  
Extension  
1" (25 mm) Space  
14 1/2"  
14 1/2"  
16 1/2"  
16 1/2"  
(368 mm)  
(368 mm)  
(419 mm) (419 mm)  
16 1/2" 19"  
(419 mm) (483 mm)  
16 1/2" 23 1/2"  
(419 mm) (579 mm)  
6/12  
14 1/2"  
(368 mm)  
17"  
(442 mm)  
Metal Safety Strip  
Platform  
Floor  
Note: Hearth extensions must not interfere with  
circulating grillwork  
12/12  
14 1/2"  
(368 mm)  
21 1/2"  
(546 mm)  
Figure 22  
* Perpendicular to roof ridge  
Figure 20  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
10  
 
Note: Install the hearth extension only as il-  
For Canadian Installations - A Cold  
Climate Kit, FTF8-CCK3-LD, must be  
installed in all indoor installations.  
lustrated (see Figures 21 & 22).  
WARNING  
The safety strips should extend from front of  
the fireplace at least 1 1/2" and should extend  
to be at least flush with the sides. In the event a  
wooden support is used to elevate the fireplace  
abovetheoor, aZtypesafetystripshouldbe  
fabricated and used to protect the front surface  
ofthewoodsupportaswellastheoorbeneath  
the hearth extension (Figures 23 & 24). The  
safety strips should be tacked down to prevent  
possible movement.  
Under no circumstances can the  
fireplacetopspacers(seeFigure  
18)beremovedormodified, nor  
may you notch the header to fit  
around or be installed lower  
than the spacers. The header  
may be in direct contact with  
the top spacers but may not be  
supported by them.  
Step5. Attachthecoldclimatekit, ModelFTF8-  
CCK1-LD, around the chimney collar with the  
screws provided (see Figure 26).  
Note: CCK1-LD model requires a 6" diameter  
Class 0 metallic air duct, acquired locally by  
installer.  
Note: The “Z” type safety strip is not sup-  
plied.  
Note: Safety strips are not required when fire-  
place rests on a noncombustible surface.  
AVERTISSEMENT  
Sous aucune circonstance les  
espaceurs du dessus du foyer  
(voir le schéma 13) ne peuvent  
être retirées ou modifiées,  
vous ne pouvez pas entaillez le  
colombage pour ajuster autour  
ou être installé plus bas que les  
espaceurs. Le colombage peut  
être en contact direct avec les  
espaceurs du dessus mais ne  
peut être soutenu par eux.  
Figure 26  
Cold Climate Kit Installation Instructions:  
1 ¹⁄₂"  
Metal Safety Strips  
1. Connect the 6" (152 mm) Class 0 metallic  
air duct to the collar on the chimney collar  
enclosure with the screws provided in the  
hardware kit. See Figure 27.  
Figure 23  
Step 4. The fireplace should be secured to the  
sideframingmembersthroughthenailingtabat  
the top and bottom on each side of the fireplace  
front face. Use 8d nails(Figure 25).  
2. Route the Class 0 metallic air duct out the  
back wall or side wall, up through the ceil-  
ing or floor joists to an outside wall. The  
air duct’s inlet should be located above any  
anticipated snow level.  
Blocking  
Note: If the fireplace is installed against an  
inside wall, the Class 0 metallic air duct may  
be extended into a ventilated attic space at  
least 18" (457 mm) above the attic floor.  
Secure the duct hood to a vertical post with  
the inlet positioned downward. Ensure that  
nothing blocks the hood opening. This air  
duct must never terminate higher than the  
fireplace chimney.  
Metal Safety Strips  
Figure 24  
Nailing Tab  
8d Nail  
Step 3. Refer to fireplace drawings and speci-  
fications (see Figures 18, 19 & 20) for fram-  
ing dimensions and details. Frame appliance  
enclosure as illustrated in Figure 18.  
Install As Shown With  
Opening In Downward  
Position Do Not Block  
Entrance  
Note: The framed depth, 20 5/8" (524 mm)  
from a framed wall, must always be measured  
from a finished surface. If a wall covering such  
as drywall is to be attached to the rear wall,  
then the 20 5/8" (524 mm) must be measured  
from the drywall surface. It is important that  
this dimension be exact.  
1/2”  
Min.  
Note: The nailing tab and the area directly  
behind the nailing tab is exempt from the  
clearancesdescribedonPage5.Maintainat  
least1/2clearancefromthereboxwrap-  
per to the framing at the closest point of  
contact, directly adjacent to the flange.  
5 Foot Min. Height  
From Outside  
Ground Level  
If the appliance is to be elevated above floor  
level, a solid continuous platform must be  
constructed.  
The header may rest on the top metal spacers,  
but must not be notched to fit around them.  
Consult all local codes.  
Figure 25  
Figure 27  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
11  
 
3. Cut or frame a hole through the outside  
wall for the installation of the duct inlet  
hood. A 6-1/2" (165 mm) diameter hole is  
required. Feed the loose end of the flexible  
duct through the hole cut for the inlet hood  
and attach to the collar on inlet hood using  
two (2) screws. Insert the hood into the  
opening. Secure in place with nails driven  
through the holes in hood flange. Seal with  
noncombustible waterproof silicon type  
caulking. If additional air duct is needed,  
use Class 0 metallic duct.  
Step 3. Position appropriate firestop spacer  
at ceiling and nail temporarily with two (2) 8d  
nails. Use flat firestop spacer, Model F8FS, if  
chimneypenetratesceilingvertically.Ifchimney  
penetratesceilingat30°angle(offsetchimney),  
use30°restopspacer,ModelF8FS30.Useone  
nail on opposite sides to hold firestop spacer in  
position.Nailpermanently,usingatleasttwo(2)  
more8dnails,afterchimneysectionshavebeen  
assembledthroughtherestopspacerandafter  
any necessary adjustments have been made.  
Firestopspacermustbesecuredbyatleastfour  
(4) 8d nails when completely installed.  
CAUTION  
Allow minimum 1"* chimney air  
space to insulation and building  
materials throughout vertical or  
offset chimney installation.  
ATTENTION  
Permettez à minimum 1 pouce*  
espace aérien de cheminée à  
l’isolation, aux matériaux de  
construction et aux membres  
encadrants dans toute la verti-  
cale ou excentrez l’installation  
de cheminée.  
Steps 6 - Install Air Gate Kit  
Notes:  
(Required on All Indoor Instlaltions. When  
an Outside Air Kit is installed, see assembly  
steps on Page 6).  
Indoor Installations: If there is a room above  
ceiling level, firestop spacer must be installed  
on the bottom side of the ceiling. If an attic is  
above ceiling level, firestop spacer must be  
installed on top side of ceiling joist (Figures  
29 & 30).  
Install the Air Gate Kit per the instructions  
provided with kit and on Page 6 (see Page 23  
for ordering information).  
Aminimum1"*airspacemustbereservedfor  
all combustible materials extending for any  
continuous length surrounding the chimney.  
Outdoor Installations: If patio installation  
requires that a chimney passes through a roof  
or room above, be sure to comply with all local  
building codes.  
Step 7. Outside Air Kit (provided)  
*Note: 2"clearancetocombustiblesrequired  
in Canada. 2” déblayage aux combustibles  
exigés au Canada.  
(Required on All Outdoor Instlaltions)  
Install the Outside Air Kit per the instructions  
provided with kit and on Page 7.  
Room Above  
ReferenceFigures19&20 andchartsFraming  
DimensionsforCeilingandRoof,whichspecify  
minimum ceiling and roof dimensions.  
Step 8. Route the Class 0 metallic air duct per  
the instructions on Page 8.  
Step 9. Cut or frame a hole through the outside  
of the enclosure for the installation of the duct  
inlet hood per the instructions on Page 8.  
Innewconstruction,todeterminechimneycenter  
line, use plumb line from roof or ceiling above  
fireplace to center of flue collar on fireplace.  
Firestop Spacer  
For remodeling, plumb to center of flue collar  
from ceiling above, drive nail through ceiling  
from below to mark position, then mark and  
cut to passage from above ceiling (around  
nail) (see Figure 28). Then plumb from ceiling  
or roof level directly above hole which has just  
been completed.  
Figure 29  
INSTALLING THE CHIMNEY SYSTEM  
Step 1. Before continuing, check the operation  
of the damper, as described on Page 5, (refer  
to Figure 3).  
Attic Above  
Step 2. Using standard construction framing  
techniques,constructopeningforchimneyroute  
up through the ceiling(s) and roof or through  
an outside chase.  
Framing must maintain adequate minimum air  
space clearance at all times.  
Firestop Spacer  
Figure 30  
Figure 28  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
12  
 
Note: Assemble one component of chimney at  
a time (inner section first, then outer section  
last) before proceeding with the next complete  
section.  
Step4.Note:Chimneysectionsareconstructed  
withauniquelockingtabdesign,whichensures  
animmediate,tightassemblybetweensections.  
Planyourchimneyrequirementscarefullybefore  
assemblyaschimneyisdifficulttodisassemble  
after installation. If disassembled, the tabs  
might become damaged. Be certain tabs are  
properly formed to ensure locking tabs engage  
properly.  
CHIMNEY 30° OFFSET THROUGH  
FLOOR OR CEILING  
It may be necessary to assemble the chimney  
at30°whenpassingthroughtheoororceiling  
area. Use the F8FS30 firestop spacer as shown  
inFigures31&32.Supportthechimneyatoor  
or ceiling penetration with a FTF8 stabilizer if  
distanceofchimneybelowceilingis10'ormore.  
Maintain1"*minimumairspacetocombustibles  
from chimney sections.  
Continue to assemble the chimney up through  
framed opening. Assemble just enough to  
penetrate the roof flashing openings (Figure  
36). Always maintain 1"* minimum air space to  
insulation and construction materials. Always  
check each chimney joint (inner and outer)  
to ensure proper engagement. Check vertical  
alignment of chimney so that it projects from  
the roof in true vertical position.  
The Security Chimney's FTF8 chimney system  
is a two piece chimney, which snap together  
from the fireplace up. Start with the inner flue  
section with the lanced end up, snap lock it in  
to the matching collar on top of the fireplace.  
At all subsequent joints, the upper flue section  
fits into the preceding flue section. Each piece  
snaps together by means of locking tabs (9  
locking tabs per joint). Check each piece by  
pullingupslightlyfromthetoptoensureproper  
engagement before installing the next section.  
If the flue has been installed correctly, it will not  
separate when you test it. Also, the inner flue  
joint where each section is joined should be  
tight and flat without gaps (Figure 34).  
Attic Space  
F8FS30  
1" Min.  
*
Firestop Spacer  
Air Space  
FTF8-S4 Stabilizer  
1" Min.  
*
Air Space  
10'  
Max.  
30 Firestop  
And Attic Above  
Figure 31  
1" Min. Air Space  
*
Room Above  
To Combustibles  
Figure 36  
F8FS30  
1" Min.  
*
Firestop Spacer  
Air Space  
Security's chimney sections do not need to be  
screwed together. Additional reinforcement is  
notnecessaryexceptincertainoffsetconditions  
(refer to Page 16, Figure 47).  
1" Min.  
*
FTF8-S4 Stabilizer  
Air Space  
Step 5. The height of vertical chimney pipe  
supportedonlybythereplacemustnotexceed  
30'. Chimney heights above 30' must be sup-  
ported by a Model FTF8-S4 stabilizer installed  
at 30' intervals.  
30 Firestop  
And Room Above  
10'  
Max.  
Figure 32  
Figure 34  
For Canada Only  
Theouterchimneysectioninstallstheopposite-  
way; the lanced end goes down and each new  
section goes OVER the outside of the previous  
section installed (Figure 35).  
Note: The Model FTF8-S4 adds 3" net effective  
height to the total chimney system.  
When installing the chimney system through  
an open attic space, the attic shield assembly-  
firestop spacer must be used (Figure 33). This  
installation is required only for use in Canada.  
Install the Model FTF8-S4 stabilizer by fitting  
inner section down into respective section of  
proceedinguepipeandlockingouterstabilizer  
section into place over the outer chimney pipe.  
Position for proper clearance through framed  
openingandnailstrapssecurely(undertension  
in “shear”) into place on framing. Use 8d nails.  
Attach successive lengths of chimney pipe  
directly to stabilizer using same techniques as  
described in Step 4 (see Figure 37).  
Open Attic Space  
Locking  
Tabs  
(Lances)  
*Notes:  
Figure 33  
• 2" clearance to combustibles required in  
Canada.  
Note: For Canadian installations, all chimney  
installed outside the building must be con-  
structed with galvalume on the outer sections  
only (Note: galvalume is galvanized). The ap-  
propriate model designations are located in the  
Figure 35  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
13  
 
Roof Ridge  
FTF8-S4 Stabilizer  
Figure 37  
120°  
Note: Do not apply excessive pressure to any  
subsequent chimney sections following the  
stabilizer when installing. Ensure each subse-  
quent chimney section is securely attached by  
testing as noted in Step 4.  
Figure 39  
Figure 41  
Step 8. The standard Security FTF8 roof flash-  
ing assemblies include a storm collar. Slide  
the storm collar over outer chimney, rest on  
flashing spacers and align with top surface of  
flashing. Insert tab in slot, pull tight and bend  
tab back over slot. Seal storm collar to outer  
chimney with roof caulking or mastic around  
entirecircumferenceofpipe.Alsoaddextraroof  
caulking to the tab/slot area to seal completely  
againstwaterpenetration(Figure40).Checkall  
jointsverycarefullytoensurenowaterintrusion  
can take place.  
Step 10. Using a FTF8-CTD or FTF8-CTDT  
Round Termination:  
1. Hold the FTF8-CTD (or CTDP) over top of  
last chimney section (Figure 42).  
2. Center inner slip section in inner flue pipe-  
slip down.  
Step 6. Select the proper Security Chimneys  
roof flashing based on pitch of roof. Use chart  
below for selection:  
Roof Pitch  
Flat to 6/12  
6/12 to 12/12  
Model  
F8F6  
F8F12  
Next,slideroofashingoverextendedchimney  
sectionthatpreviouslyhasbeeninstalledabove  
the roof opening in Step 4. FTF8 flashings  
require flashing spacers. Slide flashing all the  
way down until the flashing base rests flat on  
the roof (Figure 38). Again, check the vertical  
position of the chimney and the 1"* minimum  
air space to combustibles.  
FTF8-CTD or  
FTF8-CTDT  
Chimney  
Locking Band  
Mastic  
Termination  
Figure 42  
3. Center outer locking section over outer flue  
pipe. Push down until locking tabs are firmly  
engaged.  
FTF8 Chimney  
Do Not Seal  
4. Pull up slightly on CTD to ensure locking  
joint has firmly engaged.  
Flashing Spacers  
FTF8 Flashing  
Figure 40  
Using a FTF8-CTD, FTF8-CTDT (or CTDTM)  
Chase Termination:  
Step9.SecurityChimneyslockingbands,Model  
FLB, may be required if the chimney extends  
too high above the roof flashing. As a general  
rule, if the chimney extends more than 6' above  
the roof flashing, the use of locking bands is  
advisable to strengthen the chimney assembly.  
Align the locking band at the chimney joint.  
Locking bands wrap around pipe joints equally  
covering the joints of both pipe sections. Use  
the nut provided and TIGHTEN snugly. Do not  
overtighten as this might damage the chimney  
section (refer to Figure 40).  
Refer to specific installation instructions  
(750,014M) included with the FTF8-CTDT (or  
750,205MforFTF8-CTDTM)chasetermination  
for clearance and installation details.  
Using a FTF8-CT1 or FTF8-CT1P Chase  
Termination:  
Refer to specific installation instructions  
(750,015M) included with FTF8-CT1 chase  
terminations for clearance and installation  
details.  
Figure 38  
Note: Do not caulk or seal the ventilating open-  
ings or seal the flashing at the chimney.  
Step 7. Secure flashing by nailing along the  
perimeter into roof using 8d nails. If shingled  
roof, slide upper end and sides of roof flash-  
ing under shingles (trim if necessary), seal the  
top and both sides of the flashing to the roof  
with roof caulking. Cover nail heads with roof  
caulking (Figure 39).  
Using a FTF8-CT2 Chase Termination:  
Refer to specific installation instructions  
(750,016M) included with FTF8-CT2 chase  
terminations for clearance and installation  
details.  
Note: If chimney extends more than 8' above  
roofsurface, guywiresarealsorecommended.  
Use three (3) guy wires, attach to locking  
band assembly, extend and secure to roof in a  
triangular pattern (see Figure 41). Guy wires  
are not supplied by the manufacturer.  
Using a FTF8-CTT Chase Termination:  
Refer to specific installation instructions  
(750,077M) included with FTF8-CTT chase  
terminations for clearance and installation  
details.  
*Note: 2" clearance to combustibles required  
in Canada.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
14  
 
To determine the number of chimney sections  
and chimney components required, follow  
these steps:  
Less Than 10'  
2' Min.  
1.Determinetotalverticalheightofthereplace  
installation.Thisdimensionisthedistancefrom  
the surface the fireplace sets on to the point  
where smoke exits from the termination.  
3'  
Min  
10'  
3'  
Min  
2. Determine the number of chimney compo-  
nents required, except chimney sections. This  
wouldincluderestopspacers, stabilizers, roof  
flashing, etc.  
3. The effective heights of the components  
are:  
Figure 43  
The Fireplace  
=
=
=
=
=
=
=
=
=
36 1/4"  
10 1/4"  
16 1/4"  
341/4"  
Note: It is recommended that all exterior ex-  
posed metal fireplace components; such as  
terminations, flashings, storm collars and/or  
flue be painted with a premium quality, high  
temperature, rust preventative paint designed  
for metal. This is especially important when  
installations are made in abnormally adverse  
or corrosive environments; such as near lakes,  
oceans or in areas with consistently high  
humidity conditions. Consult the paint manu-  
facturers instructions for proper preparation  
and application.  
MULTIPLE TERMINATIONS  
FTF8-12  
If more than one termination is located in the  
same chase or within the same general prox-  
imity, we suggest they should be separated  
in distance at least 24" horizontally from flue  
center to flue center and stacked or staggered  
verticallyatleast18"apart,fromthetermination  
of one smoke exit to the termination of another  
smoke exit (Figure 44).  
FTF8-18  
FTF8-36  
FTF8-48  
46 1/4"  
4"  
FTF8-CTD Termination  
FTF8-CT1 Termination  
FTF8-CT2 Termination  
FTF8-CTDT Termination  
12" to 18"  
15" to 23"  
12" to 18"  
CTD  
TEN FOOT RULE SUMMARY  
18"  
FTF8-CTDTM Termination = 4"  
FTF8-S4 Stabilizer * 3"*  
=
The minimum chimney height above the roof  
and/or to adjacent walls and buildings is speci-  
fied by all major building codes.  
18"  
CTDT  
* Required for every 30' of vertical chimney  
and/or 10' of offset chimney.  
CTDT  
If the horizontal distance from the peak of the  
roofislessthen10',thetopofthechimneymust  
be at least 2' above the peak of the roof.  
4.Determineamountofchimneyheightrequired  
by subtracting total combined height of all pre-  
selected components (fireplace and chimney  
components from total desired height).  
24"  
24"  
Figure 44  
If the horizontal distance from the chimney  
edge to the peak of the roof is more than 10' a  
chimney height reference point is established  
on the roof surface 10' horizontally from the  
chimney edge. The top of the chimney must  
be at least 2' above this reference point. In all  
cases,thechimneycannotbelessthen3'above  
the roof at the edge of the chimney.  
ReferenceVerticalElevationChartanddetermine  
the number of chimney sections (quantity and  
length) required.  
This suggestion is provided in the interest of  
better operation. If the terminations are located  
too close to each other, smoke may migrate  
from one flue into the other.  
SPECIAL OFFSET INSTRUCTIONS  
FTF8 CHIMNEY COMPONENT  
CALCULATIONS  
To clear any overhead obstructions, you may  
offset your chimney system using Security  
Chimneys 30° offset and return elbows. Use  
two elbows - an offset elbow to initiate the  
offset and a return elbow to terminate it. A  
30° offset elbow, angling in any direction, may  
be the first component used off the top of the  
fireplace flue collar.  
The 2' in 10' rule is necessary in the interest  
of safety but does not ensure smoke-free op-  
eration. Trees, buildings, adjoining roof lines,  
adverse wind conditions, etc., may require a  
taller chimney should the fireplace not draft  
properly (refer to Figure 43).  
The minimum installed height of the completed  
fireplace system is 15' 0" for indoor installa-  
tions and 7' 3" for outdoor installations. The  
maximum height is 60' 0."  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
15  
 
The offset and return elbows may be attached  
together, or a section or sections of chimney  
may be used between, but do not exceed 20' in  
total length between elbows. If sections of pipe  
exceed10'betweenelbows,achimneystabilizer  
must be used at the midpoint (Figure 45). The  
stabilizer support straps must be attached  
under tension (in shear) to structural framing  
members above. When two sets of elbows  
are used, the maximum combined length of  
chimney used between elbows cannot exceed  
20' (Figure 46). Example: If C1 = 10' then C2  
cannot exceed 10'.  
FTF8 Vertical Elevation Chart  
FTF8 Vertical Elevation Chart  
11" to 380 1/2"  
386 1/2" to 744"  
Inches Feet/Inches 12" 18" 36" 48"  
Inches Feet/Inches 12" 18" 36" 48"  
386 ¹⁄₂  
390 ³⁄₄  
396 ³⁄₄  
404 ¹⁄₂  
414 ³⁄₄  
416 ¹⁄₂  
420 ³⁄₄  
426 ³⁄₄  
432 ³⁄₄  
437  
32 2 ¹⁄₂  
32 6 ³⁄₄  
33 0 ³⁄₄  
33 8 ¹⁄₂  
34 6 ³⁄₄  
34 8 ¹⁄₂  
35 0 ³⁄₄  
35 6 ³⁄₄  
36 0 ³⁄₄  
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
8
8
8
8
8
9
8
9
9
9
9
9
9
10  
9
11  
17  
0
1
1
2
2
3
4
4
5
5
6
6
7
8
8
9
9
9
11  
5
9 ¹⁄₄  
3 ¹⁄₄  
11  
11  
3 ¹⁄₄  
9 ¹⁄₄  
3 ¹⁄₄  
7 ¹⁄₄  
1 ¹⁄₄  
9 ¹⁄₄  
9 ¹⁄₄  
1 ¹⁄₄  
6 ¹⁄₂  
1 ¹⁄₄  
5 ¹⁄₂  
11 ¹⁄₂  
1
0
2
1
0
0
0
1
0
2
1
0
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
1
0
1
0
0
1
0
1
0
1
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
0
0
0
0
1
0
1
0
0
0
0
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
0
0
1
0
1
1
1
1
1
2
1
2
2
2
2
2
2
3
2
3
3
3
3
3
3
4
3
4
4
4
4
4
4
5
4
5
5
5
5
5
5
6
5
6
6
6
6
6
6
7
6
7
7
7
7
7
7
8
7
8
21 ¹⁄₄  
27 ¹⁄₄  
35  
47  
51 ¹⁄₄  
57 ¹⁄₄  
63 ¹⁄₄  
67 ¹⁄₄  
73 ¹⁄₄  
81 ¹⁄₄  
93 ¹⁄₄  
97 ¹⁄₄  
102 ¹⁄₂  
109 ¹⁄₄  
113 ¹⁄₂  
119 ¹⁄₂  
127 ¹⁄₄  
137 ¹⁄₂  
139 ¹⁄₄  
143 ¹⁄₂  
149 ¹⁄₂  
155 ¹⁄₂  
159 ³⁄₄  
165 ³⁄₄  
173 ¹⁄₂  
183 ³⁄₄  
185 ¹⁄₂  
189 ³⁄₄  
195 ³⁄₄  
201 ³⁄₄  
206  
36  
5
443  
36 11  
37 6 ³⁄₄  
If an offset exceeds 6' in length, each chimney  
joint beyond the first 6' of offset to the return  
elbow, must be secured by a No. 8 x 1/2" sheet  
metal screw located at the underside of the  
joint (Figure 47).  
450 ³⁄₄  
461  
462 ³⁄₄  
466 ³⁄₄  
472  
478 ³⁄₄  
483  
38  
5
38 6 ³⁄₄  
38 10 ³⁄₄  
³⁄₄ 39 4³⁄₄  
39 10 ³⁄₄  
10  
10  
10  
10  
10  
10  
11  
10  
11  
11  
11  
11  
11  
11  
12  
11  
12  
12  
12  
12  
12  
12  
13  
12  
13  
13  
13  
13  
13  
13  
14  
13  
14  
14  
14  
14  
14  
14  
15  
14  
15  
15  
15  
15  
15  
15  
16  
15  
40  
40  
3
9
489  
A 1/8" diameter hole must be drilled in the  
chimney joint using a 1/8 " diameter drill. The  
hole should be drilled in center of joint overlap  
(Figure 48). Be sure to drill only through the  
outer chimney casting. Do not puncture the  
inner flue.  
10 7 ¹⁄₄  
11 5 ¹⁄₂  
11 7 ¹⁄₄  
11 11 ¹⁄₂  
12 5 ¹⁄₂  
12 11 ¹⁄₂  
13 3 ³⁄₄  
13 9 ³⁄₄  
14 5 ¹⁄₂  
15 3 ³⁄₄  
15 5 ¹⁄₂  
15 9 ³⁄₄  
16 3 ³⁄₄  
16 9 ³⁄₄  
496 ³⁄₄  
507  
508 ³⁄₄  
513  
41 4 ³⁄₄  
42  
42 4 ³⁄₄  
3
42  
43  
43  
9
3
9
519  
525  
529 ¹⁄₄  
535 ¹⁄₄  
543  
553 ¹⁄₄  
555  
44 1 ¹⁄₄  
44 7 ¹⁄₄  
Maximum offset of chimney system is 30°.  
Two offsets must not be assembled to form  
a 60° offset. However, two sets of offset and  
return elbows may be used on a single flue  
system, provided the total height of the system  
exceeds 25'.  
45  
46 1 ¹⁄₄  
46  
3
3
559 ¹⁄₄  
565 ¹⁄₄  
571 ¹⁄₄  
575 ¹⁄₂  
581 ¹⁄₂  
589 ¹⁄₄  
599 ¹⁄₂  
601 ¹⁄₄  
605 ¹⁄₂  
611 ¹⁄₂  
617 ¹⁄₂  
621 ¹⁄₂  
627 ¹⁄₂  
635 ¹⁄₂  
645 ¹⁄₂  
647 ¹⁄₂  
651 ¹⁄₂  
657 ¹⁄₂  
663 ¹⁄₂  
667 ³⁄₄  
673 ³⁄₄  
681 ¹⁄₂  
691 ³⁄₄  
693 ¹⁄₂  
697 ³⁄₄  
703 ³⁄₄  
709 ³⁄₄  
714  
46 7 ¹⁄₄  
47 1 ¹⁄₄  
47 5 ¹⁄₄  
47 11 ¹⁄₂  
48 5 ¹⁄₂  
49 1 ¹⁄₄  
49 11 ¹⁄₂  
50 1 ¹⁄₄  
50 5 ¹⁄₂  
51 11 ¹⁄₂  
51 5 ¹⁄₂  
51 9 ¹⁄₂  
52 3 ¹⁄₂  
52 11 ¹⁄₂  
53 9 ¹⁄₂  
53 11 ¹⁄₂  
54 3 ¹⁄₂  
54 9 ¹⁄₂  
55 3 ¹⁄₂  
55 7 ³⁄₄  
56 1 ³⁄₄  
56 9 ¹⁄₂  
57 7 ³⁄₄  
57 9 ¹⁄₂  
58 1 ³⁄₄  
58 7 ³⁄₄  
59 1 ³⁄₄  
17  
17  
2
8
212  
219 ³⁄₄  
230  
231 ³⁄₄  
236  
18 3 ³⁄₄  
19  
19 3 ³⁄₄  
Return elbow support straps must be securely  
attached under tension (in shear) to structural  
framing members above. Do not substitute a  
FTF8-30 offset elbow in place of a FTF8-E30  
return elbow.  
2
19  
20  
20  
21  
21  
22  
23  
23  
23  
24  
8
2
8
0
6
2
0
2
6
0
242  
248  
252  
258  
266  
276  
278  
282  
OFFSET CALCULATIONS  
Step 1. Use the Offset Chart (Table 4) to deter-  
mineamountofhorizontaloffset(A)andheight  
(B) for various chimney section assemblies.  
288  
294 ³⁄₄  
298 ¹⁄₄  
304 ¹⁄₄  
312  
322 ¹⁄₄  
324  
328 ¹⁄₄  
334 ¹⁄₄  
340 ¹⁄₄  
344 ¹⁄₂  
350 ¹⁄₂  
358 ¹⁄₄  
368 ¹⁄₂  
370 ¹⁄₄  
374 ¹⁄₂  
380 ¹⁄₂  
24 6 ³⁄₄  
24 10 ¹⁄₄  
25 4 ¹⁄₄  
26  
26 10 ¹⁄₄  
27  
27 4 ¹⁄₄  
27 10 ¹⁄₄  
28 4 ¹⁄₄  
28 8 ¹⁄₂  
29 2 ¹⁄₂  
29 10 ¹⁄₄  
30 8 ¹⁄₂  
30 10 ¹⁄₄  
31 2 ¹⁄₂  
31 8 ¹⁄₂  
Step 2. Use “Height of Chimney Only” column  
in The Vertical Elevation Chart to determine  
combinations of chimney used above return  
elbow to achieve desired heights. Reference  
Components Effective Height Chart in vertical  
elevation chart section.  
0
0
59  
60  
6
0
720  
Step3.UseElevationChartasjobestimatoronly.  
Add necessary firestop spacers and stabilizers  
as required. Firestop spacers must be used as  
shown in Figures 31 & 32 and stabilizers as  
shown in Figure 37.  
727 ³⁄₄  
738  
739 ³⁄₄  
744  
60 7 ³⁄₄  
61  
61 7 ³⁄₄  
62  
6
0
Table 3a  
Table 3b  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
16  
 
A1  
INSTALLING OFFSETS  
First, review the Offset Elevation Chart and  
Figure 49 for reference.  
Return  
Elbow  
Joints  
20'  
Max.  
t
Step 1. Determine the offset distance where  
chimney is to pass through the first  
ceiling-dimension “A.” To find this  
point on your ceiling, first determine  
the center point for a vertical chimney  
following the instructions for vertical  
installation.  
A
'
d
6
e
Chimney  
Section  
r
t
s
i
u
a
q
P
t
e
B1  
4'  
R
n
i
s
o
J
w
e
r
y
Stabilizer  
r
c
e
S
v
E
t
e
s
n
f
I
f
d
O
e
f
No. 8 x 1/2" SMS  
r
10' Max.  
o
i
'
u
6'  
6
q
e
t
s
R
r
i
s
s
F
w
r
Measure height to the ceiling from the  
top of fireplace-dimension “B.” Use the  
appropriateOffsetElevationCharttond  
dimension “A.” Mark point where you  
will drive your nail to show the center  
point for your offset ceiling cut.  
e
o
r
Offset  
Elbow  
F
c
S
t
o
N
n
i
o
J
Figure 47  
Step 2. Proceed by using the Straight Up In-  
stallation Instructions for cutting and  
framing ceiling and roof openings.  
Figure 45  
Note: See Framing and Dimension Chart for  
the sizes of the ceiling and roof openings. The  
size of the roof opening varies with the degree  
of pitch of the roof.  
A2  
Underside Of Chimney  
C2  
B2  
Offset Elbow Assembly  
Figure 48  
A1  
Offset elbows install the same as chimney  
sections. First, snap the inner section INTO the  
preceding inner section of flue. Check connec-  
tion by pulling up slightly to ensure a tight fit.  
Next, the outer sections snap lock OVER the  
preceding outer section of chimney. Again,  
check outer section by pulling up slightly to  
ensure proper connection is made.  
FTF8-E30 Return Elbow*  
B1  
C1  
Chimney Section (S)  
B
FTF8-30 Offset Elbow*  
Return Elbow Assembly  
A
Return elbows install the same way as round  
terminations and stabilizers:  
A2  
Step 1. Hold return elbow over top of last  
chimney section.  
Step 2. Center inner slip section into inner flue  
pipe-slip down.  
C2  
B2  
Step 3. Center outer-locking section over outer  
chimney pipe. Push down until locking  
joint has firmly engaged.  
A1  
Step 4. Pullupslightlyonreturnelbowtoensure  
locking joint has firmly engaged.  
Step 5. Secure support straps to framing  
members by nailing under tension in  
sheer (Figure 50).  
*Part of Offset/Return Package Model FTF8-ES30  
B1  
Figure 49  
C1  
Figure 46  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
17  
 
Offset Elevation Chart  
A
B
FTF8-ES30  
Number of FTF8 Chimney Sections  
Offset  
Height Offset/Return FTF8-S4  
(Inches) (Inches)  
Elbow  
Stabilizer  
12"  
18"  
36"  
48"  
4
9
12  
15 ³⁄₄  
24 ¹⁄₂  
29 ³⁄₄  
33 ¹⁄₂  
38 ¹⁄₂  
43 ³⁄₄  
45 ¹⁄₄  
47 ¹⁄₂  
52 ¹⁄₂  
54 ¹⁄₄  
55 ³⁄₄  
57 ³⁄₄  
59 ¹⁄₄  
63  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
0
1
0
2
1
0
0
2
1
1
0
0
0
2
1
1
0
0
0
2
1
1
0
0
0
2
1
0
1
0
1
2
0
1
0
2
0
1
0
0
1
1
0
0
0
0
1
0
1
2
0
1
2
0
0
3
1
0
0
1
1
2
0
1
4
0
0
3
1
0
0
0
1
2
0
1
1
0
1
0
0
1
2
0
0
0
1
1
0
0
0
0
0
0
1
0
0
1
0
0
1
1
0
1
0
1
2
1
0
2
1
1
2
2
1
0
2
2
0
2
0
3
3
3
1
3
3
0
4
0
4
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
1
0
1
0
0
0
0
0
1
0
0
0
1
2
0
0
2
0
2
0
0
0
2
0
0
3
0
3
0
3
Return  
Elbow  
14 ¹⁄₄  
17 ¹⁄₄  
20 ¹⁄₄  
21  
22 ¹⁄₄  
25 ¹⁄₄  
26 ¹⁄₄  
27  
Figure 50  
Note: The return elbow assembly performs the  
samefunctionasastabilizer.Considerthiswhen  
determining the need for a stabilizer.  
Note: Do not apply excessive pressure to any  
subsequent chimney section following return  
elbow assembly when installing. Ensure that  
each subsequent chimney section is securely  
attached by testing as noted above.  
28 ¹⁄₄  
29 ¹⁄₄  
31 ¹⁄₄  
32 ¹⁄₄  
34 ¹⁄₄  
35 ¹⁄₄  
37 ¹⁄₄  
38 ¹⁄₄  
39 ¹⁄₄  
41 ¹⁄₂  
43 ¹⁄₄  
44 ¹⁄₄  
45 ¹⁄₄  
46 ¹⁄₄  
48 ¹⁄₄  
49 ¹⁄₄  
50 ¹⁄₄  
51 ¹⁄₄  
54 ¹⁄₄  
55 ¹⁄₄  
64 ¹⁄₂  
68 ¹⁄₄  
69 ³⁄₄  
73 ¹⁄₄  
75  
Gas Line Connection  
Install a 1/2" gas supply line through fireplace  
wallforconnectiontoadecorativegasappliance  
inside the firebox. Outside, the gas supply line  
connects to a gas shut-off valve recessed flush  
into the wall or floor. The valve should be con-  
trolled by a removable valve key for safety.  
77  
80 ¹⁄₂  
83 ³⁄₄  
85 ¹⁄₄  
87 ¹⁄₂  
89  
Always plumb gas line installation per local  
codes. Check all connections with a gas leak  
detection solution for leaks (which will bubble  
if present). Never test any gas line connection  
with a match or open flame.  
91 ¹⁄₂  
94 ¹⁄₄  
95 ³⁄₄  
97 ³⁄₄  
103  
104 ¹⁄₂  
56 ¹⁄₂ 106 ¹⁄₂  
This provision is intended for connection to  
a decorative gas appliance incorporating an  
automatic shut-off device and complying with  
the Standard for Decorative Gas Appliances for  
installation in vented fireplaces, ANSI Z21.60  
(1991) or American Gas Association draft re-  
quirementsforGas-FiredLogLightersforWood  
Burning Fireplaces, Draft No. 4 dated August,  
1993. Install in accordance with the National  
Fuel Gas Code, ANSI Z223.1. This complies  
with the revised U.L. 127 standard.  
58 ¹⁄₄  
61 ³⁄₄  
64 ³⁄₄  
67  
68 ³⁄₄ 128  
70  
109 ³⁄₄  
116  
121 ¹⁄₄  
124 ³⁄₄  
130  
73  
135 ¹⁄₄  
138 ¹⁄₄  
145 ¹⁄₂  
147 ¹⁄₄  
150 ³⁄₄  
74 ³⁄₄  
79  
80  
82  
82 ¹⁄₄ 152  
Table 4  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
18  
 
If you’re installing a gas line, connect it before  
the fireplace is framed and enclosed in the  
finished wall. The gas knockout is determined  
by the indentation located at the bottom and  
slightly off center in the side refractories. THE  
KNOCKOUT IS ALWAYS REMOVED FROM  
INSIDE THE FIREPLACE. DO NOT REMOVE  
THE KNOCKOUT UNLESS YOU ARE INSTALL-  
ING A GAS LINE. If removal is attempted from  
the outer wrapper, side refractory damage  
may occur. With a medium-sized hammer,  
lightly tap the surface of the indentation. The  
refractory material is very thin in this area  
and is easily removed. Once a small hole has  
been made, continue tapping until you have  
reached sufficient diameter for the gas line to  
fit through. The entire knockout does not have  
to be removed. Remove insulation in the gas  
line channel.  
Vent Free Appliances  
WARNING  
This unit has been tested and approved to  
ANSI/IAS/AGA Z21.11.2 for use with unvented  
gas appliances for INDOOR INSTALLATIONS  
ONLY and complies with the standard for Fac-  
tory-Built fireplaces, UL 127, when installed  
with unvented gas log sets.  
Unvented Gas Log Sets are not  
approved for use with fireplaces  
installed outdoors. The materials  
and components will deteriorate  
prematurely if installed outside.  
Refer to the log manufacturer’s  
literature for limitations and  
exceptions.  
Special instructions with regards to mantel  
installations must be taken into consideration  
when installing such appliances.  
The unit has been tested for use with any  
unvented log sets having a maximum rating of  
26,000 BTU in Indoor installations only. The  
minimum mantel configuration for these log  
sets are outlined in Figure 52.  
AVERTISSEMENT  
Les ensembles de bûches à gaz  
sans conduit d’évacuation ne sont  
pas approuves pour l’usage avec  
des foyers installes a l’exterieur.  
Lesmateriauxetlescomposantes  
sedeteriorerontprematurementsi  
installees a l’exterieur. Referez-  
vous a la litterature du fabricant  
des buches pour les limites et les  
exceptions.  
Log sets with 40,000 BTU may be installed  
provided that no combustible mantel projec-  
tions are placed lower than 18 inches from the  
fireplace opening.  
IMPORTANT: REPACK INSULATION MATE-  
RIAL IN SQUARE HOLE AROUND GAS LINE,  
INTERIOR AND EXTERIOR OF FIREPLACE,  
TO SEAL.  
These fireplaces have been marked with a  
maximum rating of 26,000 BTU to assure  
that homeowners do not exceed the allowable  
limits for all allowed installations of mantels.  
That limit may be increased to 40,000 BTU,  
provided that the mantel installed complies  
with the 18-inch limitation and a copy of these  
instructions are available.  
Glass Doors  
If glass doors are to be installed on these  
fireplaces, refer to specific installation instruc-  
tions packed with the glass doors. Use only  
the doors that are listed for use with these  
fireplaces. Use of other non-listed glass door  
on these fireplaces may constitute a potential  
fire hazard and is not recommended.  
CAUTION  
Plumbing connections should  
only be performed by a quali-  
fied, licensed plumber. Main  
gas supply must be off when  
plumbing gas line to fireplace  
or performing service.  
IMPORTANT  
Allowminimum1"*chimneyair  
space to combustible framing  
members throughout vertical or  
offset chimney installation.  
CAUTION  
Certain glass doors overlap the  
blackmetalfacingofthereplace.  
IFthereplacehasbeenfacedwith  
noncombustible materials, there  
might not be sufficient clearance  
to install the glass doors of your  
choice.Ensureadequateclearance  
ismaintainedatalltimessoasnot  
tointerferewiththeinstallationand  
operation of glass doors.  
ATTENTION  
Les raccordements de tuy-  
auterie devraient seulement  
etre effectues par un plombier  
qualifie et autorise. La valve  
d’alimentation de gaz princi-  
pale doit etre fermee lors de  
l’installation ou de l’entretien  
de ce foyer.  
ATTENTION  
Permettez1minimal*l’espace  
aérien de cheminée aux mem-  
bres encadrants combustibles  
partout dans vertical ou à  
l’installation de cheminée de  
rejeton.  
*Note: In Canada, a 2” clearance to com-  
bustibles is required.  
* Note : Au Canada, po. de jeu 2 aux com-  
bustibles est exigé.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
19  
 
In Canada, the minimum height for a combus-  
tiblemantelis18"(457mm)abovethereplace  
opening. Figure 51 shows typical Canadian  
installations. Combustible mantels and trim  
maybeinstalled12"abovethereplaceopening  
as per NFPA 211-latest edition and Figure 52.  
If a mantel is of a noncombustible material,  
it is exempt from these requirements as long  
as it does not interfere with the installation or  
operation of glass doors.  
ATTENTION  
WARNING  
Certaines portes de verre recou-  
vrent le revêtement noir en métal  
du foyer. SI la façade du foyer a  
étérecouverteavecdesmatériaux  
non-combustibles, il se pourrait  
qu’il n’y ait pas suffisament de  
dégagement pour installer les  
portes de verre de votre choix.  
Assurez d’avoir un dégagmet suf-  
fisant à tout moment afin de ne  
pasinterféreravecl’installationet  
l’opération des portes de verre.  
Only non-combustible materials  
are allowed on front face (front  
fireplace frame) and around the  
perimeter within 1-5/8" minimum  
on top and 1/2" on sides.  
*Note: 2" clearance to combustibles required  
in Canada.  
AVERTISSEMENT  
Note: Do not place any combustible materials  
on the fireplace face.  
Seulement on permet des matéri-  
auxnon-combustiblessurlevisage  
avant (armature avant de chemi-  
née)etautourdupérimètreàmoins  
de 1-5/8 pouces sur le dessus et  
de pouce de 1/2 des côtés.  
Finished  
Wall  
COLD CLIMATE INSULATION  
8" Max.  
(203mm)  
Combustible  
Mantel  
If you live in a cold climate, it is especially  
importanttosealallcracksaroundthereplace  
opening with noncombustible material and  
wherever cold air could enter the room. Sur-  
rounding materials must be caulked where it  
meets the black metal facing of the fireplace to  
avoid cold air intrusion. Use noncombustible  
caulkingmaterialonlyonreplacefacingtoseal.  
Also,theoutsideairinletductshouldbewrapped  
with noncombustible insulation to minimize  
the formation of condensation. Do not place  
insulationmaterialsontopofreplaceoragainst  
chimney sections. If gas logs are installed, the  
gas line holes and other openings should be  
caulked with high temperature caulk or stuffed  
with unfaced fiberglass insulation.  
Header  
Top Spacer  
Hearth Extensions and Wall Shields  
on Appliance  
1-5/8" Min.  
A hearth extension must be installed with  
all fireplaces. It is to protect the combustible  
floor in front of the fireplace from both radiant  
heat and sparks. The hearth extension must  
extend 8" beyond both sides of the fireplace  
opening and 16" beyond the front (see Figure  
53). Use a hearth extension constructed of a  
durable noncombustible material having an  
equalorbetter(lowerkvalue)insulatingvalueof  
k=.84BTUIN/FT2HR°Forathermalresistance  
that equals or exceeds r = 1.19 HR °F FT2/BTU  
IN. With these values, determine the minimum  
thickness/material required using the formula  
and Table 5 on Page 21.  
18" Max.  
(457mm)  
Fireplace  
Opening  
The shaded gray area showing 1-5/8" Min.  
indicates non-combustible materal is required.  
Figure 51 - Canadian Installation  
Note: A 1"* air space must be preserved for all  
insulation and construction materials extend-  
ing for any continuous length adjacent to the  
chimney.  
12"  
Finished  
Wall  
Max.  
Note: Any noncombustible material having  
a thickness of 1" whose k value is less than  
.84 or whose r value is more than 1.19 is ac-  
ceptable.  
Combustible  
Mantel  
Itisespeciallyimportanttoinsulatebetweenthe  
studs of an outside chase cavity and under the  
floor if the floor is above ground level. Do not  
place insulation directly against the fireplace  
or chimney system.  
and Trim  
1 1/2"  
Header  
If the fireplace is installed on a combustible  
floor, use the metal safety strips (provided)  
on the floor extending half under the fireplace  
and half under the hearth extension (refer to  
Figures 21 & 22).  
1-5/8" Min.  
Spacer  
12"*  
Min.  
FIREPLACE FINISHES  
Mantels and Trim  
9-5/8"*  
Min.  
Itissometimesbesttoframeyourreplaceafter  
it is positioned and the chimney is installed.  
Frameenclosureforchimneyandreplacewith  
2 x 4’s (or heavier) lumber.  
A wall shield is required where a continuous  
perpendicular side wall is within 12" of the  
fireplace opening (Figure 53). Use a 24" W x  
30"Hx1/2"wallshieldconstructedofadurable,  
noncombustible material having an equal or  
better (lower k value) insulating value than  
k = .54 BTU IN/FT2 HR °F. At no time may a  
perpendicular side wall be located closer than  
7" from the fireplace opening.  
Fireplace  
Opening  
*Both Of These Dimensions Must Be At Least 18”  
When An Unvented Gas Log Set Rated At 26,000  
BTU Or Higher Is Used. (Maximum 40,000 BTU).  
Note: The header may touch but not rest its  
weight on the two (2) metal top spacers on top  
of the unit. The header must not be notched to  
fit around the spacers.  
The shaded gray area showing 1-5/8" Min.  
indicates non-combustible materal is required.  
These fireplaces may sit directly on a com-  
bustible surface. A 1"* air space is required  
between insulation and building materials  
and the chimney. A 1" air space is required  
between combustible framing and fireplace  
outer wrapper.  
Figure 52 - Typical Installation  
If fireplace is installed diagonally across a 90°  
corner; no wall shields are required.  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
20  
 
Wall Shield Required  
Where Less Than 12"  
Hearth Extension Dimensions  
24"  
A
B
C
D
16"  
30"  
8"  
30"  
46"  
C
C
B
D
Note: To convert inches to millimeters divide by .03937.  
C
A
B
D
Figure 53  
C
A
Methods of Determining Hearth Extension and Wall Shield  
Listed Material  
Equivalents - To determine the thickness required for the alternate  
material when either the "k" value or "r" value is known, use either the  
k formula or r formula.  
k (per inch) r (per inch)  
Listed Min.Thickness  
Listed Material  
.84  
1.19  
rL  
1"  
KL  
TL  
Example: If Micore 160 is to be used for the hearth extension fireplace,  
how thick must this material be?  
** Approved Alternate Materials for Floor/Hearth Protection  
AlternativeMaterials  
Thermal Values  
MinimumThickness  
(rounded to nearest 1/8 inch)  
kM = k value per inch of alternate material  
rM = r value per inch of alternate material  
TM = minimum thickness required for alternate material  
TS = standard thickness of the alternate material  
k (per inch) r (per inch)  
Min. Thickness  
KM  
rM  
TM  
Kaowool M Board  
.47  
.35  
2.13  
2.86  
.56" (1/2")  
.42" (3/8")  
Micore 160™  
U.S. Gypsum  
kL = k value per inch of listed material  
rL = r value per inch of listed material  
TL = minimum thickness of listed material  
Micore 300™  
U.S. Gypsum  
.46  
2.17  
.52  
.55" (1/2")  
Durock™ Cement Board  
U.S. Gypsum  
1.92  
2.29" (2-1/4")  
Note: An asterix "*" indicates, it is a value taken from Table 5.  
Using the k formula:  
Hardibacker™  
1.95  
2.30  
2.82  
.513  
.435  
.355  
2.32" (2-3/8")  
2.74" (2-3/4")  
3.36" (3-3/8")  
Hardibacker 500™  
Minimum  
k-value (per Inch) of  
alternate material (kM) x  
k-value (per inch)  
Specified min.  
thickness  
thickness of  
alternate  
=
Cultered Stone Hearth-  
stone™  
of listed  
material (TM)  
of listed material (kL)  
material (TL)  
Wonderboard  
3.23  
.61  
.31  
3.85" (3-7/8")  
.73" (3/4")  
Super Firetemp M  
Johns-Manville  
1.64  
TM (inches)  
=
=
k
M
x
x
x
TL  
1"  
1"  
*.84  
Super Firetemp L  
Johns-Manville  
.54  
1.85  
.64" (5/8")  
TM (inches)  
*.35  
*.84  
Face brick  
9.00  
5.00  
5.00  
12.5  
~11  
.111  
.20  
10.71" (10-3/4")  
5.95" (6")  
Common brick  
Cement mortar  
Ceramic tile  
Marble  
.416 (inches)=  
.416  
.20  
5.95" (6")  
.08  
14.88" (14-7/8")  
13.10" (13-1/8")  
Answer -TheminimumrequiredthicknessoftheMicore160is.417,"there-  
fore round up to nearest standard thickness available which is 1/2."  
~.09  
Table 5  
Using the r formula:  
Minimum  
thickness of  
alternate  
material  
r-value (per Inch)  
of listed material  
r-value (per inch)  
of alternate material  
Specified min.  
thickness  
of listed  
** If the hearth extension material(s) that is intended to be used is NOT listed  
on Table 5, the material can still be used if the material(s) is noncombustible.  
However,themanufacturerofthematerialmustprovideeitherthelistedk-value  
per inch or r-value per inch with listed thickness so that the minimum thickness  
required for the hearth can be calculated (per instructions on this Page and/or  
as specified in the NFI Certification manuals).  
=
x
x
material  
rL  
rM  
TM (inches)  
=
=
TL  
Note: Also see NFI (National Fireplace Institute) Certification Manuals showing  
other exceptable caluculation methods and acceptable alternate materials  
which can be used.  
TM (inches)  
*1.19  
* 2.86  
x
x
1"  
1"  
.417 (inches)=  
.416  
Answer -TheminimumrequiredthicknessoftheMicore160is.417,"there-  
fore round up to nearest standard thickness available which is 1/2."  
21  
 
Calculating Minimum Thickness if  
Multiple Materials are Used  
WARNING  
The crack between the fireplace  
andthehearthextensionmustbe  
sealed with a noncombustible  
material.  
At times it is important to know what  
combinationofmaterialsareacceptableforuse  
as floor protection. The “R values” are used to  
determineacceptablecombinationsofmaterials  
because “R values” are additive where r and k  
values are not.  
7"  
Max. Thickness Of Hearth Extension When  
Non-Circulating Models Are On The Floor  
AVERTISSEMENT  
“R value” = 1/k = "r" x thickness of material  
used  
La fente entre le foyer et  
l’extension d’âtre doit être  
scellée avec un matériel non-  
combustible.  
Figure 54  
Example: Given that the required “R value”  
for a suitable floor protector used must be  
equal to or greater than:  
Secure the hearth extension to the floor to  
prevent possible shifting.  
“R” = rL x TL = 1.19 x 1” = 1.19."  
If it is desired to elevate a marble hearth  
extension to a level of 5” or more above  
the floor surface. What combination of  
noncombustible materials can be used to  
accomplish this?  
FINISH TO YOUR TASTE  
WARNING  
There are a wide variety of “finished looks” for  
these fireplaces, from formal wall decor with  
elaborate mantels to rustic wood paneling or  
warm brick facings.  
When installing hearth extension  
in front of a non-circulating fire-  
place model, the fireplace must be  
raised if height of hearth extension  
exceeds 7" above the bottom of  
fireplace (Figure 54).  
If common brick is used so that the 3 1/2”  
dimension is the height, “R” for the common  
Only noncombustible materials like stone, tile,  
brick, etc., may overlap the black front facing.  
Do not extend these materials beyond the black  
facing and into the firebox area. Be sure not to  
interfere with the installation and operation of  
glass doors or block the upper or lower grilles.  
Seal all joints between the black facing and  
wall surrounds to prevent air intrusion. Use  
noncombustible caulking material only to seal  
the black metal facing to the surround material  
on the finished wall.  
brick becomes:  
brick  
“R”M = rM x TS = 0.20 x 3 1/2" = .70  
Using 1/2” of mortar to set the brick, “R” for  
the mortar is calculated as follows:  
mortar  
When installing the hearth exten-  
sion be careful not to block the  
heat-circulating air inlet grill on  
circulating models.  
“R”M = rM x TS = 0.20 x 1/2" = .10  
Next, a 3/4" marble slab set in 1/2" mortar cov-  
ers the brick, “R” for the marble and mortar  
becomes:  
AVERTISSEMENT  
Combustible materials may project beyond the  
sides of the fireplace opening as long as they  
are kept within the shaded areas illustrated in  
Figure 55.  
marble  
Eninstallantlaprolongationdefoyer  
devant un modèle decirculation de  
cheminée, la cheminée doit être  
augmentée si la taille de la prolon-  
gation de foyer excède 7”(pouces)  
au-dessus du fond de la cheminée  
(Figure 54).  
“R”M = rM x TS = 0.05 x 3/4" = .038  
mortar  
“R”M = rM x TS = 0.20 x 1/2" = .10  
The sum of all “R values” is: .70 + .10 +. 038  
+ .10 = .938  
Combustible Ma-  
terials Allowed In  
This would NOT be an acceptable combination  
of material for the hearth extension since the  
total calculated “R value” of the materials used  
is under the required “R value” of 1.19. An  
additional layer of insulating materials must  
be used.  
Fireplace  
1"  
1/2"  
ShadedArea“Safe  
Zone”  
7"  
45°  
Eninstallantl’extensiond’âtrefaites  
attention à ne pas bloquer la grille  
d’entrée d’air sur les modèles à  
circulation d’air.  
12"  
Min. Distance To  
Protected Side Wall  
7"  
Note: Also see NFI Certification Manuals for  
expanded explanation on calculating “R val-  
ues” when multiple materials are used.  
12"  
Min. Distance To  
Unprotected Side Wall  
Figure 55  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
22  
 
INSTALLATION COMPONENTS  
The following items are available for use in the  
installation of this appliance.  
Locking Band  
63L60  
FLB  
Firestop Spacer (Flat) (Single Pack) 63L29  
Firestop Spacer (Flat) (Single Pack) 63L31  
F8FS  
F8FS-2  
Firestop Spacer (Flat) (12 Pack)  
94L76  
F8FS-12  
Firestop Spacer (30°)  
Firestop Spacer (30°)  
Firestop Spacer (45°) (Canadian) 63L33  
63L30  
63L32  
F8FS30  
F8FS30-2  
FFS-45C  
Storm Collar  
Storm Collar (12 pack) 94L77  
63L59  
FSC  
FSC-B-12  
Spark Arrestor  
(CT2 Termination)  
63L57  
FSA-2  
Offset/ Return  
Package (30°)  
45° Offset/Return Package  
(Canadian) 63L69  
63L22  
FTF8-ES30  
FTF8-ES45C  
Ref. Form #750,012M  
Combination  
Offset/Return Elbow  
63L28  
FTF8-OR15  
Ref. Form #750,141M  
H1935  
36ABFOD-BS 36” Bi-Fold door, Stainless  
Stabilizer  
63L25  
FTF8-S4  
(Air Inlet supplied with  
fireplace. Shownhereforre-  
placement purposes only)  
Ref. Form #750,191M  
Outside Air Kit  
H1964  
OAK-OD  
Ref. Form #750,140M  
63L38  
63L39  
F8F6  
F8F12  
H1937 36-ODC  
36” Stainless Weather Cover  
Flashing  
Chimney Section  
63L10  
63L13  
H0522  
63L14  
63L15  
FTF8-12  
FTF8-18  
FTF8-24  
FTF8-36  
FTF8-48  
Ref. Form #750,198M  
Air Gate is shown apart for illustration purposes only.  
Air Gate Kit H1972 OAKG-OD  
Ref. Form #750,080M  
Canadian  
Chimney Section  
62L92  
62L93  
FTF8-18C  
FTF8-36C  
Cold Climate Kits  
63L61  
FTF8-CCK1-LD  
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.  
23  
 
Contains:  
3
1
1
1
FTF8-36  
F8FS  
F8F6  
F
T
F
8
7
-
P
C
I
C
P
-
8
7
F
T
F
S
U
P
A
R
R
U
Y
L
B
M
C
E
S
S
FTF8-CTD  
H
I
M
N
E
B
Y
Y
L
E
N
M
I
H
A
C
S
S
E
M
Y
A
B
Contemporary Termination -  
Round  
63L42  
FTF8-CTD  
Contemporary Termination -  
Chimney Pack (conventional)  
Convenience Pack - Residential 63L70  
D
Round, Black  
H2238  
FTF8-CTDP  
FTF8-CP7  
C
Ref. Form #750,194M  
CLOSED TOP SHROUD TERMINATION KITS  
Inches (millimeters)  
Cat. #  
Model  
A
B
C
D
Ref. Form #750,036M  
34"  
5"  
34"  
34"  
H1988 CTSA-33  
(864) (127) (864) (864)  
Chase Termination  
(Round)  
8” Arch Top Termination  
H0203  
FTF8-CTDTM  
(For shrouds closed above) 96L22  
FTF8-ATT  
1
typ.  
CTSO-46 Shroud  
for double  
terminations  
2a  
2b  
C
2a  
E
2b  
2a  
D
Ref. Form #750,015M  
Chase Termination - Pyramid  
2b  
2a  
(Square)  
63L48  
FTF8-CT1  
FTF8-CT1P  
B
Ref. Form #750,016M  
Chase Termination - Pyramid, Black  
A
Chase Termination  
(Square)  
(Square)  
91L79  
63L51  
FTF8-CT2  
C
1
typ.  
typ.  
2
E
D
Ref. Form #750,034M  
Attic Shield Assembly  
4 ea. Shroud Legs  
63L67  
FTF8-FSAS  
B
A
Ref. Form #750,077M  
CTSO-33/44 Shrouds  
for Single terminations  
8” Open Top Termination (clay top termination)  
(For open top shrouds) 96L20 FTF8-CTT  
Ref. Form #750,193M  
OPEN TOP SHROUD KITS  
Inches (millimeters)  
Cat. #  
Model  
A
B
C
D
*E  
37-5/8  
(955)  
37-5/8  
(955)  
7-1/2 In.  
(191)  
24-1/2  
(622)  
3 In.  
(76)  
H1985 CTSO-33  
H1987 CTSO-44  
H1986 CTSO-46  
4 ea. Flashing  
Spacers  
48-5/8  
(1235)  
48-5/8  
(1235)  
7-1/2 In.  
(191)  
24-1/2  
(622)  
3 In.  
(76)  
Ref. Form #750,014M  
Ref. Form #750,145M  
48-5/8  
(1235)  
73 1/4  
(1860)  
7-1/2 In.  
(191)  
24-1/2  
(622)  
3 In.  
(76)  
Termination Shroud Leg Kit  
H0911 SLK-4  
Chase Termination  
(Round)  
63L45  
FTF8-CTDT  
The manufacturer reserves the right to make changes at any time, without notice, in design,  
materials, specifications, prices and also to discontinue colors, styles and products.  
Consult your local distributor for fireplace code information.  
Printed in U.S.A. © 2005 by LENNOX HEARTH PRODUCTS  
1110 West Taft Avenue  
Orange, CA 92865  
24  
P/N 850,030M REV. B 04/2006  
 

La Crosse Technology Battery Charger BC 900 User Manual
Lantronix Planer UBOX4100 User Manual
Lindy Computer Monitor 21519CH User Manual
Lumex Syatems Mobility Aid 604070A User Manual
Mackie Music Mixer SW0194 92 User Manual
Makita Cordless Drill 6411 User Manual
Mattel Doll Y8517 User Manual
Maytag Clothes Dryer MDG120 User Manual
Mellerware Bread Maker 26550550W User Manual
Meridian America Telephone Accessories 555 8421 211 User Manual