Lennox Hearth Indoor Fireplace RDI 42 User Manual

INSTALLATION  
INSTRUCTIONS  
MERIT® SERIES  
42" Wood Burning Fireplaces  
P/N 850,047M REV. B 12/2008  
MODELS  
RDI-42  
HCI-42  
RDI-42-H  
HCI-42-H  
This installation manual will enable you to obtain a safe, efficient and  
dependable installation of your fireplace system. Please read and under-  
stand these instructions before beginning your installation.  
Do not alter or modify the fireplace or its components under any  
circumstances. Any modification or alteration of the fireplace system,  
including but not limited to the fireplace, chimney components and  
accessories, may void the warranty, listings and approvals of this system  
and could result in an unsafe and potentially dangerous installation.  
IMPORTANT! TO ASSURE PROPER ALIGNMENT OF GLASS DOORS:  
INSTALL THIS FIREPLACE IN A SQUARE AND PLUMB CONDITION,  
USING SHIMS AS NECESSARY AT SIDES AND/OR BOTTOM.  
INSTALLER: Leave this manual with the appliance.  
CONSUMER: Retain this manual for future reference.  
Portland  
OMNI Report No. 116-F-52-2  
US  
 
Note: Illustrations shown reflect typical”  
installations with nominal dimensions and  
are for design and framing reference only.  
Actual installations may vary due to indi-  
vidual design preferences. However, always  
maintain minimum clearances to combus-  
tible materials and do not violate any spe-  
cific installation requirements.  
PRECAUTIONS  
WARNING: FAILURE TO USE MANUFAC-  
TUREPROVIDEDPARTS, VARIATIONSIN  
TECHNIQUES AND CONSTRUCTION MA-  
TERIALS OR PRACTICES OTHER THAN  
THOSE DESCRIBED IN THIS MANUAL  
MAY CREATE A FIRE HAZARD AND VOID  
THE LIMITED WARRANTY.  
Note: These fireplace systems are not difficult  
to install. However, in the interest of safety, it is  
recommendedthattheinstallerbeaqualifiedor  
certified tradesman” familiar with commonly  
accepted fireplace installation and safety tech-  
niques as well as prevailing local codes.  
The most important areas of concern dealing  
withtheinstallationoffactory-builtfireplacesare  
clearances to combustible materials, proper as-  
sembly of component parts, height of the chim-  
ney system, the proper use of accessories sup-  
plied by the manufacturer and the techniques  
employed in using finishing materials applied to  
the wall surrounding the fireplace, hearth exten-  
sions and wall shields. Each of these topics will  
be covered in thorough detail throughout this  
manual. Please give each your special attention  
as you progress with your installation.  
These fireplaces have been tested and  
listed by Omni-Test Laboratories (Report  
No. 116-F-52-2) to U.L. standard 127.  
These units are intended for installation  
in residential homes and other buildings  
of conventional construction including  
commercial, not in mobile homes.  
When complete these fireplace systems con-  
sists of four basic sub-systems:  
1. The Fireplace  
2. The Chimney and Termination  
3. The Optional Glass Doors  
4. The Optional Combustion Air Kits  
5. Optional Cold Climate Kit (Mandatory in  
Canada).  
These fireplaces have been tested for instal-  
lation in Canada to ULC-S610. For installa-  
tions in Canada, the chimney clearance to  
combustibles must be 2 inches and the  
Cold Climate Kit must be installed.  
CLEARANCES AND HEIGHT  
REQUIREMENTS  
The fireplace may be placed on or near normal  
constructionmaterials*. Thecombustionairkit,  
firestop spacer and roof flashing (not chase  
flashings) may be placed directly on or against  
normal construction materials.* The chimney  
requires a minimum 2" air space clearance to  
combustibles. The fireplace outer wrapper  
requires a minimum 1" air space clearance to  
combustibles. A combustible mantle may be  
installed12"abovetheopeningofthefireplaceas  
per NFPA 211, Section 7-2.3.3. In Canada, the  
minimum is 18" above the fireplace opening.  
INTRODUCTION  
General Information  
These fireplace systems are designed for  
installation in accordance with the National  
Fire Protection Standard for chimneys, fire-  
places and solid fuel burning appliances;  
NFPA 211 and in accordance with codes  
such as the BOCA Basic/National Codes, the  
Standard Mechanical Code and the Uniform  
Building Codes.  
These fireplaces are conventional radiant heat  
fireplaces with standard bar grates, optional  
outside combustion air kits and optional deco-  
rative glass doors.  
The "C" models are designed as heat circulating  
fireplacesandmaybefittedwithaccessoryfans.  
TYPICAL INSTALLATION  
Theminimuminstalledheightofthecompleted  
fireplacesystemis15' 0". Themaximumheight  
is 60' 0".  
The fireplace and chimney system must be  
enclosed when installed in or passing through  
alivingareawherecombustiblesorpeoplemay  
come in contact with it. This is important to  
prevent possible personal injury or fire hazard.  
Blower Kit  
(Optional)  
Chimney and  
Termination  
Chimney and  
Termination  
For questions, please call your distributor or  
the manufacturer. Special restrictions apply to  
the front and facing of the fireplace and nearby  
walls (See pages 16, 17 and 18 ).  
Outside  
CHIMNEY SYSTEM  
Combustion  
Air Kit  
Outside  
Combustion  
Air Kit  
(Optional)  
These fireplaces are designed and code listed  
for use with Security Chimneys FTF8 chimney  
System only. Always use Security Chimneys  
FTF8 chimney components with these fire-  
places. Do not modify or alter these compo-  
nents as this may cause a potential serious  
hazard and void the Warranty.  
(Optional)  
Radiant Model Shown  
Figure 1  
Circulating Model Shown  
*Construction Materials:  
• framing materials • paneling  
• particle board  
• dry wall  
• flooring  
etc.  
• plywood  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
3
 
Chimney Height  
LOCATION OF FIREPLACE  
Insulate Joists  
Same As Ceiling  
The total height of your completed fireplace  
system from the surface the fireplace rests on  
to the chimney top must not exceed 60' and  
mustalsomeetminimumheightrequirements.  
Refer to the minimum system height chart.  
Carefully select the proper location for heat  
circulation, aesthetics, chimney obstructions  
andclearancetosidewall(s). Withproper pre-  
planning, a slight adjustment of a few inches  
can save considerable time and expense later  
during construction and assembly.  
Draft Stops  
Firestop  
Minimum System Height  
Security's FTF8 Pipe  
Vertical Installation  
One Offset  
15' 0"  
15' 0"  
25' 0"  
CTDT  
Termination  
Hearth  
Hearth  
Note: Non-  
Combustible  
Chase  
Flashing  
Must Be  
Used To  
Cover  
Chase  
Opening  
Two Offsets  
Chase Enclosure  
A chase is a vertical box-like structure con-  
structedtosurroundthefireplaceandchimney.  
Refer to Figure 2 for a typical chase configura-  
tion. As with all chimney installations, avoid  
overhead obstructions such as trees, power  
lines, etc. A chase should be constructed and  
insulated just like any outside wall. In a cold  
climate, we recommend the base of the chase  
should also be insulated between the solid  
continuous floor beneath the fireplace and the  
chase bottom. Chase insulation in a cold cli-  
mate installation is not required for safety.  
Optional  
Outside Chase  
Figure 4  
Optional  
Insulation  
In Outside  
Walls Of  
Chase  
Carefully consider the position of the fireplace  
opening with respect to the location of adja-  
cent or nearby stairwells, bath or kitchen ex-  
haustfansand/orreturnairregistersforforced  
air furnaces/air conditioners that could cause  
a smoking fireplace condition if the house is  
tightly insulated.  
8'  
Level  
Solid  
Continuous  
Surface  
ASSEMBLY OUTLINE  
Before You Start  
Outside  
Base  
Whenlocatingthefireplace,considerationmust  
be given to combustibles and final finishing.  
See Figure 5 and confine the final location of  
combustiblefinishmaterialstothe"SafeZone".  
Insulation  
(Thermal Barrier)  
Check your inventory list to be sure you have all  
the necessary parts supplied in good usable  
condition.Checkalsoforanyconcealeddamage.  
Figure 2  
DO NOT permanently place furniture or other  
items such as decorative pillows within 60" of  
the fireplace front face.  
WARNING: IF INSULATION IS USED, THE  
FIREPLACE MUST NOT BE PLACED DI-  
RECTLY AGAINST IT. INSULATION OR  
VAPORBARRIERS, IFUSED, MUSTFIRST  
BE COVERED WITH GYPSUM BOARD,  
PLYWOOD, PARTICLEBOARDOROTHER  
MATERIALTOASSUREINSULATIONAND  
VAPOR BARRIERS REMAIN IN PLACE.  
Checktheoperationofthedamper.Thedamper  
is controlled through the use of a control lever  
located within the firebox opening at the top  
centerjustbehindthefireboxlintel(Figure3).  
The control lever snaps into place at the ex-  
treme range of motion, up and back in the  
closed position. When pulled forward and  
down, the damper is open.  
Black Portion Of Frame  
Not To Be Covered With  
Combustible Materials  
Wall  
Covering  
12”  
45°  
WARNING: DO NOT PACK OR FILL RE-  
QUIRED AIR SPACES WITH INSULATION  
OR OTHER MATERIAL. NO MATERIAL IS  
ALLOWED IN THESE AREAS.  
1”  
Damper  
Closed  
Damper  
Open  
Door  
Opening  
Safe  
Zone  
Lintel  
12”  
Note: Do not insulate the chase cavity with  
blown or fill type insulation materials.  
Figure 5  
Combustion  
Air Actuator  
Note:Localcodesmaynotrequirefirestopping  
at the ceiling levels for outside chase installa-  
tions. However, it is recommended for safety  
and the reduction of heat loss.  
Figure 3  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
4
 
1. Estimate the total weight of the fireplace  
system including chimney and surround ma-  
terials such as brick, stone, etc., to be in-  
stalled. Shipping weights for the fireplace  
may be found on page 18.  
ASSEMBLY STEPS  
Top  
Spacers  
Note:Thefollowingstepsrepresentthenormal  
sequence of installation. Each installation is  
unique, however, and might require a different  
sequence.  
Maintain  
1" (25 mm)  
Air Space  
At Back  
And Sides  
2. Measure the square footage of the floor  
spacetobeoccupiedbythesystem, surrounds  
and hearth extensions.  
1. Position firebox prior to framing or into  
prepared framing.  
Hearth  
Extension  
3. Notethefloorconstruction,i.e.2x6’s,2x8’s  
or 2 x 10’s, single or double joists, type and  
thickness of floor boards.  
2. Install the chimney system.  
1" (25 mm) Space  
3. Connect house wiring to the fireplace for  
later attachment of optional blower.  
Metal Safety Strip  
Floor  
4. Use this information and consult your local  
building code to determine if you need addi-  
tional support.  
4. Install optional outside combustion air kit.  
Note: Hearth extensions must not interfere with  
circulating grillwork  
5. Plumb gas line if a decorative gas appliance  
will be used. (Gas connections should only be  
performed by an experienced, licensed/certi-  
fied tradesman.)  
Figure 6  
CAUTION: DO NOT BLOCK THE HEAT-CIRCU-  
LATING AIR INLET AND OUTLET PORTS ON  
CIRCULATING MODELS. DOING SO MAY RE-  
SULT IN A POTENTIAL FIRE HAZARD.  
Top  
Spacers  
6. Complete the installation, finish wall mate-  
rial, surround and hearth extension to your  
individual taste.  
Maintain  
1" (25 mm)  
Air Space  
At Back  
If you plan to raise the fireplace and hearth  
extension, build the platform assembly then  
position fireplace and hearth extension on top.  
Secure the platform to the floor to prevent  
possible shifting.  
And Sides  
7. Assemble and attach optional glass door  
assembly.  
CLEARANCES  
Study the three dimensional illustration (Fig-  
ure 1 ) to get a general idea of each element of  
your fireplace system.  
Hearth  
Extension  
1" (25 mm) Space  
Minimum clearance to combustibles for the  
applianceisasfollows:sidesandback- 1"(25  
mm),floor-0"(0mm),adjacentwall-12"(305  
mm), ceiling - 37-1/2" (953 mm).  
PRE-INSTALLATION NOTES  
Metal Safety Strip  
Platform  
Floor  
The fireplace may be installed directly on a  
combustiblefloor or raisedonaplatformof an  
appropriate height. Do not place fireplace on  
carpeting,vinylorothersoftfloorcoverings.It  
may, however, be placed on flat wood, ply-  
wood, particle board or other hard surfaces.  
Be sure fireplace rests on a solid continuous  
floor or platform with appropriate framing for  
support and so that no cold air can enter the  
room from under the fireplace.  
INSTALLING THE FIREPLACE  
Note: Hearth extensions must not interfere with  
circulating grillwork  
Step 1. Slide the fireplace into prepared fram-  
ing or position fireplace in its final position and  
frame later.  
Figure 7  
Note: Install the hearth extension only as illus-  
trated.  
The fireplace may not be recessed into a com-  
bustiblefloor.Maintainthefloortohearthclear-  
ance established by the fireplace lower front  
face.  
The safety strips should extend from front of  
thefireplaceatleast1-1/2"andshouldextendto  
be at least flush with the sides. In the event a  
wooden support is used to elevate the fireplace  
abovethefloor,a“Ztypesafetystripshouldbe  
fabricated and used to protect the front surface  
ofthewoodsupportaswellasthefloorbeneath  
the hearth extension (Figures 8 and 9 ). The  
safety strips should be tacked down to prevent  
possible movement.  
The fireplace may be positioned and then the  
framing built around it, or the framing may be  
constructed and the fireplace positioned into  
the opening.  
Step 2. Insert the provided metal safety strips,  
beneath the fireplace as illustrated (Figures 6,  
7 and 8 ). The safety strips should overlap 1/2"  
for continual coverage of the floor.  
Usually, no special floor support is needed for  
the fireplace, however, to be certain:  
Note: Safety strips are not required when fire-  
place rests on a noncombustible surface.  
Note: The Z type safety strip is not supplied.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
5
 
FIREPLACE SPECIFICATIONS  
12-1/2"  
(318 mm)  
8-3/8"  
(213 mm)  
16-5/16"  
(414 mm)  
1-1/2"  
Metal Safety Strips  
41"  
(1041 mm)  
46-3/8"  
(1178 mm)  
40-1/2"  
22-5/16"  
2-7/8"  
(73 mm)  
Figure 8  
(1029 mm)  
(566 mm)  
7-3/4"  
(197 mm)  
Blocking  
46-3/4"  
(1187 mm)  
Front  
Fireplace Top Spacers  
1/2"  
(13 mm)  
Metal Safety Strips  
Figure 9  
Combustion  
Air Inlet  
9-7/8"  
(251 mm)  
Step 3. Refer to fireplace drawings and specifi-  
cationsonpages6and7forframingdimensions  
and details. Frame appliance enclosure as illus-  
trated in Figures 11 through 14 on page 8.  
Gas Line  
Access  
46-3/8"  
(1178 mm)  
41-3/8"  
(1051 mm)  
10"  
(254 mm)  
IMPORTANT: UNDER NO CIRCUMSTANCES  
CAN THE FIREPLACE TOP SPACERS (FIGURE  
10 ) BE REMOVED OR MODIFIED, NOR MAY  
YOUNOTCHTHEHEADERTOFITAROUNDOR  
BE INSTALLED LOWER THAN THE SPACERS.  
THE HEADER MAY BE IN DIRECT CONTACT  
WITH THE TOP SPACERS BUT MAY NOT BE  
SUPPORTED BY THEM.  
40-1/2"  
(1029 mm)  
Gas Line  
Access  
17-5/16"  
(439 mm)  
13-5/8"  
(346 mm)  
Junction  
Box  
23-1/2"  
(597 mm)  
22-7/8"  
(581 mm)  
Note: The framed depth, 23-7/8" (606 mm)  
from a framed wall, must always be measured  
from a finished surface. If a wall covering such  
asdrywallistobeattachedtotherearwall,then  
the 23-7/8" (606 mm) must be measured from  
the drywall surface. It is important that this  
dimension be exact.  
Left Side  
Right Side  
31-9/16"  
(802 mm)  
Fireplace  
Top Spacer  
8-1/2"  
(216 mm)  
23-1/2"  
(597 mm)  
If the appliance is to be elevated above floor  
level, a solid continuous platform must be  
constructed.  
12-1/2"  
(318 mm)  
1-3/4"  
(44 mm)  
The header may rest on the top metal spacers,  
but must not be notched to fit around them.  
46-3/4"  
(1187 mm)  
50-1/4"  
(1276 mm)  
Consult all local codes.  
Top View  
Figure 10  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
6
 
FRAMING SPECIFICATIONS  
Framing Dimensions  
C
D
A
B
C
D
E
F
49"  
1245 mm  
Back Wall of  
Chase/Enclosure  
Including Finising  
Materials  
FOAK Combustion  
Air Kit - Optional  
46-1/2" 1181 mm  
if any  
33"  
17-1/2" 445 mm  
81" 2057 mm  
40-3/8" 1026 mm  
838 mm  
J
F
Header  
A
E
G
H
J
24"  
23"  
607 mm  
584 mm  
Rough  
Framing Face  
(Unfinished Shown)  
B
Corner Installation  
57-1/4" 1454 mm  
Figure 14  
Note: All framing dimensions calcu-  
lated for 5/8" nailing flange depth and  
1/2" dry wall at the fireplace face. If  
sheathing the chase or finishing with  
otherthicknessmaterials,calculations  
will need to be made.  
A
Fireplace Framing  
Figure 11  
Note: A, C and G dimensions include  
1" clearance to combustibles.  
Back Wall of Chase/Enclosure  
Including Finising Materials if any  
FOAK Combustion  
Air Kit  
Framing Dimensions for Ceiling  
B
Flue Type  
A
B
A
G
Ceiling Framing  
FTF8 Vertical  
16-1/2"  
16-1/2"  
(419 mm) (419 mm)  
A
Rough  
Framing Face  
(Unfinished Shown)  
Figure 15  
FTF8 Offset 30° 16-1/2"  
27"  
Inside Chase  
(419 mm) (686 mm)  
Figure 12  
Back Wall of Chase/Enclosure  
Including Finising Materials  
if any  
FOAK  
Combustion  
Air Kit - Optional  
Framing Dimensions for Roof  
Pitch  
0/12  
C
D*  
16-1/2"  
16-1/2"  
G
H
(419 mm)  
(419 mm)  
A
6/12  
16-1/2"  
19"  
C
Rough  
(419 mm)  
(483 mm)  
D
Framing Face  
Outside Chase  
(Unfinished Shown)  
Roof Framing  
12/12  
16-1/2"  
23-1/2"  
(419 mm)  
(597 mm)  
Figure 13  
Figure 16  
* Perpendicular to roof ridge  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
7
 
Step 4. Fireplace should be secured to side  
framing members using the nailing tabs at the  
top and bottom of the fireplace front face. Use  
8d nails or equivalent (Figure 17 ).  
Step 7. Route the Class 0 metallic air duct out  
thebackwallorsidewall,upthroughtheceiling  
or floor joists to an outside wall. The air duct’s  
inlet should be located above any anticipated  
snow level.  
Note: If the fireplace is installed against an  
inside wall, the Class 0 metallic air duct may be  
extendedintoaventilatedatticspaceatleast18"  
(457 mm) above the attic floor. Secure the duct  
hood to a vertical post with the inlet positioned  
downward.Ensurethatnothingblocksthehood  
opening. This air duct must never terminate  
higher than the fireplace chimney.  
8d Nail Or  
Equivalent  
Step 8. Cut or frame a hole through the outside  
wall for the installation of the duct inlet hood. A  
6-1/2" (165 mm) diameter hole is required.  
Feed the loose end of the flexible duct through  
the hole cut for the inlet hood and attach to the  
collaroninlethoodusingtwo(2)screws.Insert  
the hood into the opening. Secure in place with  
nails driven through the holes in hood flange.  
Seal with noncombustible waterproof silicon  
type caulking. If additional air duct is needed,  
use Class 0 metallic duct.  
Figure 19  
Step 3. Position appropriate firestop spacer at  
ceiling and fasten temporarily with two (2) 8d  
nails or equivalent. Use flat firestop spacer,  
Model F8FS-2, if chimney penetrates ceiling  
vertically. If chimney penetrates ceiling at 30°  
angle(offsetchimney),use30°firestopspacer,  
Model F8FS30-2. Use one nail on opposite  
sidestoholdfirestopspacerinposition. Fasten  
permanently, using at least two (2) more 8d  
nailsorequivalent,afterchimneysectionshave  
been assembled through the firestop spacer  
andafteranynecessaryadjustmentshavebeen  
made. Firestop spacer must be secured by at  
least four (4) 8d nails or equivalent when com-  
pletely installed.  
Figure 17  
Note: The nailing tabs and the area directly  
behind the nailing tabs are exempt from the  
clearances described on page 5. Maintain at  
least 1" clearance from the firebox wrapper to  
the framing at the closest point of contact,  
directly adjacent to the flange.  
INSTALLING THE CHIMNEY SYSTEM  
Step 1. Before continuing, check the operation  
ofthedamper, asdescribedonpage4, (referto  
Figure 3 ).  
For Canadian Installations Proceed  
with Steps 5 through 8  
Step 5. Attach the cold climate kit, Model  
CCK-HCRD, around the chimney collar with  
the screws provided (see Figure 18 ).  
Step 2. Using standard construction framing  
techniques,constructopeningforchimneyroute  
upthroughtheceiling(s)androoforthroughan  
outside chase.  
Note: If there is a room above ceiling level,  
firestopspacermustbeinstalledonthebottom  
side of the ceiling. If an attic is above ceiling  
level, firestop spacer must be installed on top  
side of ceiling joist (Figures 20 and 21 ).  
Note: CCK-HCRD model requires a 6" diameter  
Class 0 metallic air duct, acquired locally by  
installer.  
Framing must maintain adequate minimum air  
space clearance at all times.  
Chimney Duct  
Duct Collar  
CAUTION: ALLOW MINIMUM 2" CHIMNEY  
AIRSPACETOCOMBUSTIBLEFRAMINGMEM-  
BERS THROUGHOUT VERTICAL OR OFFSET  
CHIMNEY INSTALLATION.  
Room Above  
Front Cover  
Plate “ A”  
A minimum 2" air space must be reserved for  
all combustible materials extending for any  
continuous length surrounding the chimney.  
Firestop Spacer  
ReferenceFigures15and16 andchartsFram-  
ing Dimensions for Ceiling and Roof, which  
specify minimum ceiling and roof dimensions.  
Figure 20  
Front Cover  
Plate “ B”  
Attic Above  
Front Cover Plate “ A”  
Knockout  
In new construction, to determine chimney cen-  
terline,useplumblinefromrooforceilingabove  
fireplace to center of flue collar on fireplace.  
Figure 18  
Step 6. Connect the 6" (152 mm) Class 0  
metallic air duct to the collar on the chimney  
collar enclosure with the screws provided in  
the hardware kit.  
For remodeling, plumb to center of flue collar  
from ceiling above, drive nail through ceiling  
frombelowtomarkposition,thenmarkandcut  
to passage from above ceiling (around nail)  
(see Figure 19 ). Then plumb from ceiling or  
roof level directly above hole which has just  
been completed.  
Firestop Spacer  
Figure 21  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
8
 
Step 4. Note: Chimney sections are con-  
structed with a unique locking tab design,  
which ensures an immediate, tight assembly  
between sections. Plan your chimney require-  
ments carefully before assembly as chimney  
is difficult to disassemble after installation. If  
disassembled, the tabs might become dam-  
aged. Be certain tabs are properly formed to  
ensure locking tabs engage properly.  
Note: Assemble one component of chimney at  
a time (inner section first, then outer section  
last) before proceeding with the next complete  
section.  
CHIMNEY 30° OFFSET THROUGH FLOOR  
OR CEILING  
Itmaybenecessarytoassemblethechimneyat  
30° when passing through the floor or ceiling  
area. Use the F8FS30-2 firestop spacer as  
shown in Figures 22 and 23. Support the  
chimney at floor or ceiling penetration with a  
FTF8 stabilizer if distance of chimney below  
ceiling is 10' or more. Maintain 2" minimum air  
space to combustibles from chimney sections.  
Continue to assemble the chimney up through  
framed opening. Assemble just enough to pen-  
etrate the roof flashing openings (Figure 27 ).  
Always maintain 2" minimum air space to com-  
bustiblematerialsandalwayscheckeachchim-  
ney joint (inner and outer) to ensure proper  
engagement.Checkverticalalignmentofchim-  
ney so that it projects from the roof in true  
vertical position.  
The Security FTF8 chimney system is a two  
piece chimney, which snap together from the  
fireplace up. Start with the inner flue section  
with the lanced end up, snap lock it in to the  
matching collar on top of the fireplace. At all  
subsequent joints, the upper flue section fits  
into the preceding flue section. Each piece  
snaps together by means of locking tabs (9  
locking tabs per joint). Check each piece by  
pullingupslightlyfromthetoptoensureproper  
engagement before installing the next section.  
Ifthefluehasbeeninstalledcorrectly, itwillnot  
separate when you test it. Also, the inner flue  
joint where each section is joined should be  
tight and flat without gaps (Figure 25 ).  
Attic Space  
F8FS30-2  
Firestop Spacer  
2" Min.  
Air Space  
FTF8-S4 Stabilizer  
2" Min.  
Air Space  
10'  
Max.  
30° Firestop  
1"* Min. Air Space  
To Combustibles  
And Attic Above  
Figure 22  
Figure 27  
Room Above  
Security's chimney sections do not need to be  
screwed together. Additional reinforcement is  
not necessary except in certain offset condi-  
tions (refer to page 14, Figure 38 ).  
F8FS30-2  
Firestop Spacer  
2" Min.  
Air Space  
Step 5. The height of vertical chimney pipe  
supported only by the fireplace must not ex-  
ceed 30'. Chimney heights above 30' must be  
supported by a Model FTF8-S4 stabilizer in-  
stalled at 30' intervals.  
2" Min.  
Air Space  
FTF8-S4 Stabilizer  
30° Firestop  
10'  
Max.  
And Room Above  
Note: The Model FTF8-S4 adds 3" net effective  
height to the total chimney system.  
Figure 23  
Figure 25  
For Canada Only  
Outer pipe section installs in just the opposite  
way; the lanced end goes down and each new  
section goes OVER the outside of the previous  
section installed (Figure 26 ).  
Install the Model FTF8-S4 stabilizer by fitting  
inner section down into respective section of  
proceeding flue pipe and locking outer stabi-  
lizer section into place over the outer chimney  
pipe. Position for proper clearance through  
framedopeningandnailstrapssecurely(under  
tension in shear) into place on framing. Use  
8d nails. Attach successive lengths of chimney  
pipe directly to stabilizer using same tech-  
niques as described in Step 4 (Figure 28 ).  
Wheninstallingthechimneysystemthroughan  
open attic space, the attic shield assembly-  
firestop spacer must be used (Figure 24 ). This  
installation is required only for use in Canada.  
Open Attic Space  
Locking  
Tabs  
(Lances)  
Figure 24  
Figure 26  
Note: For Canadian installations, all chimney  
installedoutsidethebuildingmustbeconstructed  
with galvalume (outer sections only) effective  
January 1, 1992. The appropriate model desig-  
nations are located in the back of this manual.  
FTF8-S4 Stabilizer  
Figure 28  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
9
 
Note: Do not apply excessive pressure to any  
subsequent chimney sections following the  
stabilizer when installing. Ensure each subse-  
quent chimney section is securely attached by  
testing as noted in Step 4.  
Step 8. Slide the FTF8 storm collar (ordered  
separately) over outer chimney, rest on flash-  
ing spacers and align with top surface of flash-  
ing. Insert tab in slot, pull tight and bend tab  
back over slot. Seal storm collar to outer chim-  
ney with roof caulking or mastic around entire  
circumference of pipe. Also add extra roof  
caulking to the tab/slot area to seal completely  
against water penetration (Figure 31 ). Check  
all joints very carefully to ensure no water  
intrusion can take place.  
Step10.UsingaFTF8-CTDRoundTermination:  
1. Hold the FTF8-CTD over top of last chimney  
section (Figure 33 ).  
2. Center inner slip section in inner flue pipe-  
slip down.  
Step 6. Select the proper Security roof flash-  
ing based on pitch of roof. Use chart below for  
selection:  
3. Center outer locking section over outer flue  
pipe. Push down until locking tabs are firmly  
engaged.  
Roof Pitch  
Model  
F8F6  
Flat to 6/12  
6/12 to 12/12  
F8F12  
Locking Band  
Next,slideroofflashingoverextendedchimney  
sectionthatpreviouslyhasbeeninstalledabove  
the roof opening in Step 4. FTF8 flashings  
require flashing spacers. Slide flashing all the  
way down until the flashing base rests flat on  
the roof (Figure 29 ). Again, check the vertical  
positionofthechimneyandthe2"minimumair  
space to combustibles.  
Waterproof  
Caulk  
CTD  
Termination  
Chimney  
Figure 33  
4. PullupslightlyonCTDtoensurelockingjoint  
has firmly engaged.  
Figure 31  
FTF8 Chimney  
Do Not Seal  
Step 9. Security Chimneys locking bands,  
Model FLB, may be required if the chimney  
extends too high above the roof flashing. As a  
general rule, if thechimneyextendsmorethan  
6' above the roof flashing, the use of locking  
bands is advisable to strengthen the chimney  
assembly. Align the locking band at the chim-  
ney joint. Locking bands wrap around pipe  
joints equally covering the joints of both pipe  
sections. Use the nut provided and TIGHTEN  
snugly. Do not overtighten as this might dam-  
age the chimney section (refer to Figure 31 ).  
Using a FTF8-CTDT Chase Termination:  
Flashing Spacers  
FTF8 Flashing  
Refer to specific installation instructions in-  
cluded with the FTF8-CTDT chase termination  
for clearance and installation details.  
Using a FTF8-CT1 Chase Termination:  
Figure 29  
Refer to specific installation instructions in-  
cluded with FTF8-CT1 chase terminations for  
clearance and installation details.  
Note: Do not caulk or seal the ventilating open-  
ings.  
Using a FTF8-CT2 Chase Termination:  
Note: If chimney extends more than 8' above  
roofsurface, guywiresarealsorecommended.  
Use three (3) guy wires, attach to locking band  
assembly, extend and secure to roof in a trian-  
gular pattern (Figure 32 ). Guy wires are not  
supplied by the manufacturer.  
Step 7. Secure flashing by nailing along the  
perimeterintoroofusing8dnailsorequivalent.  
If shingled roof, slide upper end and sides of  
roof flashing under shingles (trim if neces-  
sary),sealthetopandbothsidesoftheflashing  
to the roof with roof caulking. Cover nail heads  
with roof caulking (Figure 30 ).  
Refer to specific installation instructions in-  
cluded with FTF8-CT2 chase terminations for  
clearance and installation details.  
Using a FTF8-CTT Chase Termination:  
Roof Ridge  
Refer to specific installation instructions in-  
cluded with FTF8-CTT chase terminations for  
clearance and installation details.  
Using a FTF8-ATT Chase Termination:  
Refer to specific installation instructions in-  
cluded with FTF8-ATT chase terminations for  
clearance and installation details.  
120°  
Figure 32  
Figure 30  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
10  
 
To determine the number of chimney sections  
and chimney components required, follow  
these steps:  
Less Than 10'  
2' Min.  
1. Determine total vertical height of the fireplace  
installation. This dimension is the distance from  
the surface the fireplace sets on to the point  
where smoke exits from the termination.  
3'  
Min  
10'  
3'  
Min  
2. Determine the number of chimney compo-  
nents required, except chimney sections. This  
wouldincludefirestopspacers,stabilizers,roof  
flashing, etc.  
3. The effective heights of the components are:  
Figure 34  
The Fireplace  
=
=
=
=
=
=
=
=
=
=
=
=
45-3/8"  
10-1/4"  
16-1/4"  
34-1/4"  
46-1/4"  
4"  
FTF8-12  
Note: It is recommended that all exterior ex-  
posed metal fireplace components; such as  
terminations, flashings, storm collars and/or  
flue be painted with a premium quality, high  
temperature, rust preventative paint designed  
for metal. This is especially important when  
installationsaremadeinabnormallyadverseor  
corrosive environments; such as near lakes,  
oceans or in areas with consistently high hu-  
midity conditions. Consult the paint manufac-  
turers instructions for proper preparation and  
application.  
MULTIPLE TERMINATIONS  
FTF8-18  
If more than one termination is located in the  
samechaseorwithinthesamegeneralproxim-  
ity, we suggest they should be separated in  
distance at least 24" horizontally from flue cen-  
ter to flue center and stacked or staggered  
vertically at least 18" apart, from the termina-  
tion of one smoke exit to the termination of  
another smoke exit (Figure 35 ).  
FTF8-36  
FTF8-48  
FTF8-CTD Termination  
FTF8-CT1 Termination  
FTF8-CT2 Termination  
FTF8-CTDT Termination  
FTF8-CTT Termination  
FTF8-ATT Termination  
FTF8-S4 Stabilizer *  
12" to 18"  
15" to 23"  
12" to 18"  
6" to 14"  
8" to 14"  
3"*  
CTD  
18"  
TEN FOOT RULE SUMMARY  
18"  
The minimum chimney height above the roof  
and/or to adjacent walls and buildings is speci-  
fied by all major building codes.  
CTDT  
* Required for every 30' of vertical chimney  
and/or 10' of offset chimney.  
CTDT  
If the horizontal distance from the peak of the  
roof is less then 10', the top of the chimney  
must be at least 2' above the peak of the roof.  
4. Determine amount of chimney height re-  
quired by subtracting total combined height of  
all pre-selected components (fireplace and  
chimneycomponentsfromtotaldesiredheight.)  
24"  
24"  
If the horizontal distance from the chimney  
edge to the peak of the roof is more than 10' a  
chimney height reference point is established  
on the roof surface 10' horizontally from the  
chimney edge. The top of the chimney must be  
at least 2' above this reference point. In all  
cases, the chimney cannot be less then 3'  
above the roof at the edge of the chimney.  
Figure 35  
Reference Vertical Elevation Chart and deter-  
minethenumberofchimneysections(quantity  
and length) required.  
This suggestion is provided in the interest of  
betteroperation. Iftheterminationsarelocated  
too close to each other, smoke may migrate  
from one flue into the other.  
SPECIAL OFFSET INSTRUCTIONS  
To clear any overhead obstructions, you may  
offset your chimney system using Security's  
30° offset and return elbows. Use two elbows -  
anoffsetelbowtoinitiatetheoffsetandareturn  
elbow to terminate it. A 30° offset elbow, an-  
gling in any direction, may be the first compo-  
nent used off the top of the fireplace flue collar.  
FTF8 CHIMNEY COMPONENT  
CALCULATIONS  
The 2' in 10' rule is necessary in the interest of  
safety but does not ensure smoke-free opera-  
tion. Trees, buildings, adjoining roof lines, ad-  
versewindconditions, etc., mayrequireataller  
chimney should the fireplace not draft properly  
(see Figure 34 ).  
The minimum installed height of the com-  
pleted fireplace system is 15' 0". The maxi-  
mum height is 60' 0".  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
11  
 
The offset and return elbows may be attached  
together, or a section or sections of chimney  
may be used between, but do not exceed 20' in  
total length between elbows. If sections of pipe  
exceed 10' between elbows, a chimney stabi-  
lizer must be used at the midpoint (Figure 36 ).  
The stabilizer support straps must be attached  
under tension (in shear) to structural framing  
members above. When two sets of elbows are  
used, the maximum combined length of chim-  
ney used between elbows cannot exceed 20'  
(Figure37).Example:IfC =10' thenC cannot  
FTF8 VERTICAL ELEVATION CHART  
Height Of  
Chimney Only  
Number Of FTF8  
Chimney Lengths  
Height Of  
Chimney Only  
Number Of FTF8  
Chimney Lengths  
Inches Feet/Inches 12" 18" 36" 48"  
Inches Feet/Inches 12" 18" 36" 48"  
386 ¹⁄₂  
390 ³⁄₄  
396 ³⁄₄  
404 ¹⁄₂  
414 ³⁄₄  
416 ¹⁄₂  
420 ³⁄₄  
426 ³⁄₄  
432 ³⁄₄  
437  
443  
450 ³⁄₄  
461  
462 ³⁄₄  
466 ³⁄₄  
472  
478 ³⁄₄  
483  
32 2 ¹⁄₂  
32 6 ³⁄₄  
33 0 ³⁄₄  
33 8 ¹⁄₂  
34 6 ³⁄₄  
34 8 ¹⁄₂  
35 0 ³⁄₄  
35 6 ³⁄₄  
36 0 ³⁄₄  
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
8
8
8
8
8
9
8
9
9
9
9
9
9
10  
9
11  
17  
0
1
1
2
2
3
4
4
5
5
6
6
7
8
8
9
9
9
11  
5
1
0
2
1
0
0
0
1
0
2
1
0
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
2
1
0
1
0
0
1
0
1
0
1
0
0
1
0
1
0
1
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
0
0
0
0
1
0
1
0
0
0
0
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
1
1
0
1
0
0
0
0
0
0
1
0
1
1
1
1
1
2
1
2
2
2
2
2
2
3
2
3
3
3
3
3
3
4
3
4
4
4
4
4
4
5
4
5
5
5
5
5
5
6
5
6
6
6
6
6
6
7
6
7
7
7
7
7
7
8
7
8
21 ¹⁄₄  
27 ¹⁄₄  
35  
9 ¹⁄₄  
3 ¹⁄₄  
11  
11  
3 ¹⁄₄  
9 ¹⁄₄  
3 ¹⁄₄  
7 ¹⁄₄  
1 ¹⁄₄  
9 ¹⁄₄  
9 ¹⁄₄  
1 ¹⁄₄  
6 ¹⁄₂  
1 ¹⁄₄  
5 ¹⁄₂  
11 ¹⁄₂  
47  
51 ¹⁄₄  
57 ¹⁄₄  
63 ¹⁄₄  
67 ¹⁄₄  
73 ¹⁄₄  
81 ¹⁄₄  
93 ¹⁄₄  
97 ¹⁄₄  
102 ¹⁄₂  
109 ¹⁄₄  
113 ¹⁄₂  
119 ¹⁄₂  
127 ¹⁄₄  
137 ¹⁄₂  
139 ¹⁄₄  
143 ¹⁄₂  
149 ¹⁄₂  
155 ¹⁄₂  
159 ³⁄₄  
165 ³⁄₄  
173 ¹⁄₂  
183 ³⁄₄  
185 ¹⁄₂  
189 ³⁄₄  
195 ³⁄₄  
201 ³⁄₄  
206  
1
2
exceed 10'.  
36  
5
36 11  
37 6 ³⁄₄  
If an offset exceeds 6' in length, each chimney  
joint beyond the first 6' of offset to the return  
elbow, must be secured by a No. 8 x 1/2" sheet  
metalscrewlocatedattheundersideofthejoint  
(Figure 38 ).  
38  
5
38 6 ³⁄₄  
38 10 ³⁄₄  
³⁄₄ 39 4³⁄₄  
39 10 ³⁄₄  
10  
10  
10  
10  
10  
10  
11  
10  
11  
11  
11  
11  
11  
11  
12  
11  
12  
12  
12  
12  
12  
12  
13  
12  
13  
13  
13  
13  
13  
13  
14  
13  
14  
14  
14  
14  
14  
14  
15  
14  
15  
15  
15  
15  
15  
15  
16  
15  
40  
40  
3
9
489  
496 ³⁄₄  
507  
508 ³⁄₄  
513  
519  
10 7 ¹⁄₄  
11 5 ¹⁄₂  
11 7 ¹⁄₄  
11 11 ¹⁄₂  
12 5 ¹⁄₂  
12 11 ¹⁄₂  
13 3 ³⁄₄  
13 9 ³⁄₄  
14 5 ¹⁄₂  
15 3 ³⁄₄  
15 5 ¹⁄₂  
15 9 ³⁄₄  
16 3 ³⁄₄  
16 9 ³⁄₄  
41 4 ³⁄₄  
42  
42 4 ³⁄₄  
A 1/8" diameter hole must be drilled in the  
chimney joint using a 1/8" diameter drill. Hole  
should be drilled in center of joint overlap  
(Figure 39 ). Be sure to drill only through the  
outer chimney casting. Do not puncture the  
inner flue.  
3
42  
43  
43  
9
3
9
525  
529 ¹⁄₄  
535 ¹⁄₄  
543  
553 ¹⁄₄  
555  
44 1 ¹⁄₄  
44 7 ¹⁄₄  
45  
46 1 ¹⁄₄  
46  
3
Maximumoffsetofchimneysystemis30°.Two  
offsets must not be assembled to form a 60°  
offset. However, two sets of offset and return  
elbows may be used on a single flue system,  
providedthetotalheightofthesystemexceeds  
25'.  
3
559 ¹⁄₄  
565 ¹⁄₄  
571 ¹⁄₄  
575 ¹⁄₂  
581 ¹⁄₂  
589 ¹⁄₄  
599 ¹⁄₂  
601 ¹⁄₄  
605 ¹⁄₂  
611 ¹⁄₂  
617 ¹⁄₂  
621 ¹⁄₂  
627 ¹⁄₂  
635 ¹⁄₂  
645 ¹⁄₂  
647 ¹⁄₂  
651 ¹⁄₂  
657 ¹⁄₂  
663 ¹⁄₂  
667 ³⁄₄  
673 ³⁄₄  
681 ¹⁄₂  
691 ³⁄₄  
693 ¹⁄₂  
697 ³⁄₄  
703 ³⁄₄  
709 ³⁄₄  
714  
46 7 ¹⁄₄  
47 1 ¹⁄₄  
47 5 ¹⁄₄  
47 11 ¹⁄₂  
48 5 ¹⁄₂  
49 1 ¹⁄₄  
49 11 ¹⁄₂  
50 1 ¹⁄₄  
50 5 ¹⁄₂  
51 11 ¹⁄₂  
51 5 ¹⁄₂  
51 9 ¹⁄₂  
52 3 ¹⁄₂  
52 11 ¹⁄₂  
53 9 ¹⁄₂  
53 11 ¹⁄₂  
54 3 ¹⁄₂  
54 9 ¹⁄₂  
55 3 ¹⁄₂  
55 7 ³⁄₄  
56 1 ³⁄₄  
56 9 ¹⁄₂  
57 7 ³⁄₄  
57 9 ¹⁄₂  
58 1 ³⁄₄  
58 7 ³⁄₄  
59 1 ³⁄₄  
17  
17  
2
8
212  
219 ³⁄₄  
230  
18 3 ³⁄₄  
19  
19 3 ³⁄₄  
2
231 ³⁄₄  
236  
19  
20  
20  
21  
21  
22  
23  
23  
23  
24  
8
2
8
0
6
2
0
2
6
0
242  
248  
252  
258  
266  
276  
278  
282  
Return elbow support straps must be securely  
attached under tension (in shear) to structural  
framing members above. Do not substitute a  
FTF8-30 offset elbow in place of a FTF8-E30  
return elbow.  
288  
OFFSET CALCULATIONS  
294 ³⁄₄  
298 ¹⁄₄  
304 ¹⁄₄  
312  
322 ¹⁄₄  
324  
328 ¹⁄₄  
334 ¹⁄₄  
340 ¹⁄₄  
344 ¹⁄₂  
350 ¹⁄₂  
358 ¹⁄₄  
368 ¹⁄₂  
370 ¹⁄₄  
374 ¹⁄₂  
380 ¹⁄₂  
24 6 ³⁄₄  
24 10 ¹⁄₄  
25 4 ¹⁄₄  
26  
26 10 ¹⁄₄  
27  
27 4 ¹⁄₄  
27 10 ¹⁄₄  
28 4 ¹⁄₄  
28 8 ¹⁄₂  
29 2 ¹⁄₂  
29 10 ¹⁄₄  
30 8 ¹⁄₂  
30 10 ¹⁄₄  
31 2 ¹⁄₂  
31 8 ¹⁄₂  
Step 1. Use Offset Chart to determine amount  
of horizontal offset (A) and height (B) for vari-  
ous chimney section assemblies.  
0
0
Step 2. Use Height of Chimney Only” column  
in The Vertical Elevation Chart to determine  
combinations of chimney used above return  
elbow to achieve desired heights. Reference  
Components Effective Height Chart in vertical  
elevation chart section.  
59  
60  
6
0
720  
727 ³⁄₄  
738  
739 ³⁄₄  
744  
60 7 ³⁄₄  
61  
61 7 ³⁄₄  
62  
6
0
Step 3. Use Elevation Chart as job estimator  
only. Add necessary firestop spacers and sta-  
bilizers as required. Firestop spacers must be  
used as shown in Figures 22 and 23 and  
stabilizers as shown in Figure 28.  
12  
 
A1  
OFFSET ELEVATION CHART  
A
Offset  
B
FTF8-ES30  
Number of FTF8 Chimney Sections  
Return  
Elbow  
Height Offset/Return FTF8-S4  
(Inches) (Inches)  
Elbow  
Stabilizer  
12"  
18"  
36"  
48"  
20'  
Max.  
4
15 ³⁄₄  
24 ¹⁄₂  
29 ³⁄₄  
33 ¹⁄₂  
38 ¹⁄₂  
43 ³⁄₄  
45 ¹⁄₄  
47 ¹⁄₂  
52 ¹⁄₂  
54 ¹⁄₄  
55 ³⁄₄  
57 ³⁄₄  
59 ¹⁄₄  
63  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
0
1
0
2
1
0
0
2
1
1
0
0
0
2
1
1
0
0
0
2
1
1
0
0
0
2
1
0
1
0
1
2
0
1
0
2
0
1
0
0
1
1
0
0
0
0
1
0
1
2
0
1
2
0
0
3
1
0
0
1
1
2
0
1
4
0
0
3
1
0
0
0
1
2
0
1
1
0
1
0
0
1
2
0
0
0
1
1
0
0
0
0
0
0
1
0
0
1
0
0
1
1
0
1
0
1
2
1
0
2
1
1
2
2
1
0
2
2
0
2
0
3
3
3
1
3
3
0
4
0
4
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
1
0
1
0
0
0
0
0
1
0
0
0
1
2
0
0
2
0
2
0
0
0
2
0
0
3
0
3
0
3
9
12  
B1  
Stabilizer  
14 ¹⁄₄  
17 ¹⁄₄  
20 ¹⁄₄  
21  
10' Max.  
22 ¹⁄₄  
25 ¹⁄₄  
26 ¹⁄₄  
27  
Offset  
Elbow  
28 ¹⁄₄  
29 ¹⁄₄  
31 ¹⁄₄  
32 ¹⁄₄  
34 ¹⁄₄  
35 ¹⁄₄  
37 ¹⁄₄  
38 ¹⁄₄  
39 ¹⁄₄  
41 ¹⁄₂  
43 ¹⁄₄  
44 ¹⁄₄  
45 ¹⁄₄  
46 ¹⁄₄  
48 ¹⁄₄  
49 ¹⁄₄  
50 ¹⁄₄  
51 ¹⁄₄  
54 ¹⁄₄  
55 ¹⁄₄  
64 ¹⁄₂  
68 ¹⁄₄  
69 ³⁄₄  
73 ¹⁄₄  
75  
Figure 36  
A2  
77  
80 ¹⁄₂  
83 ³⁄₄  
85 ¹⁄₄  
87 ¹⁄₂  
89  
C
2
B2  
A1  
91 ¹⁄₂  
94 ¹⁄₄  
95 ³⁄₄  
97 ³⁄₄  
103  
B1  
C
1
104 ¹⁄₂  
56 ¹⁄₂ 106 ¹⁄₂  
58 ¹⁄₄  
61 ³⁄₄  
64 ³⁄₄  
67  
109 ³⁄₄  
116  
121 ¹⁄₄  
124 ³⁄₄  
68 ³⁄₄ 128  
A2  
70  
130  
73  
135 ¹⁄₄  
138 ¹⁄₄  
145 ¹⁄₂  
147 ¹⁄₄  
150 ³⁄₄  
74 ³⁄₄  
79  
C
2
B2  
80  
A1  
82  
82 ¹⁄₄ 152  
B1  
C
1
Figure 37  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
13  
 
Step 5. Secure support straps to framing  
members by nailing under tension in sheer  
(Figure 41 ).  
INSTALLING OFFSETS  
First, review the Offset Elevation Chart and  
Figure 38 for reference.  
Joints  
Step 1. Determine the offset distance where  
chimney is to pass through the first ceiling-  
dimension A.” To find this point on your ceil-  
ing, first determine the center point for a verti-  
cal chimney following the instructions for ver-  
tical installation.  
Chimney  
Section  
4'  
y Joint Past 6'  
Screws Required At  
Ever  
No. 8 x 1/2" SMS  
6'  
Return  
Elbow  
Measure height to the ceiling from the top of  
fireplace-dimension B.” Use the appropriate  
Offset Elevation Chart to find dimension A.”  
Mark point where you will drive your nail to  
showthecenterpointforyouroffsetceilingcut.  
No Screws Required In  
Joints For First 6' of Offset  
Figure 41  
Note: The return elbow assembly performs the  
same function as a stabilizer. Consider this  
when determining the need for a stabilizer.  
Figure 38  
Step2. ProceedbyusingtheStraightUpInstal-  
lation Instructions for cutting and framing ceil-  
ing and roof openings.  
Note: Do not apply excessive pressure to any  
subsequent chimney section following return  
elbow assembly when installing. Ensure that  
each subsequent chimney section is securely  
attached by testing as noted above.  
Note:SeeFramingandDimensionChartforthe  
sizes of the ceiling and roof openings. The size  
of the roof opening varies with the degree of  
pitch of the roof.  
OPTIONAL EQUIPMENT  
CONSIDERATIONS  
Underside Of Chimney  
Offset Elbow Assembly  
Offset elbows install the same as chimney  
sections. First, snap the inner section INTO the  
preceding inner section of flue. Check connec-  
tion by pulling up slightly to ensure a tight fit.  
Next, the outer sections snap lock OVER the  
preceding outer section of chimney. Again,  
check outer section by pulling up slightly to  
ensure proper connection is made.  
Blower Kits (Circulating Models Only)  
Figure 39  
Blower Kits model FBK-100/200 are available  
for use with circulating models. The Blower  
Kit can be installed prior to or after installation  
of the fireplace.  
FTF8-E30 Return Elbow*  
Chimney Section (S)  
Note: These fireplace models require a wall  
switch for fan operation. Refer to the installa-  
tion instructions included with the Blower Kits  
for installation details.  
Return Elbow Assembly  
B
FTF8-30 Offset Elbow*  
Return elbows install the same way as round  
terminations and stabilizers:  
THE FIREPLACE MUST BE WIRED TO THE  
HOUSE ELECTRICAL SYSTEM AT THE TIME  
OF INSTALLATION IN ORDER FOR THE OP-  
TIONAL FANS TO OPERATE, (SEE FIGURES  
42 AND 43 ).  
A
Step 1. Hold return elbow over top of last  
chimney section.  
Step 2. Center inner slip section into inner flue  
pipe-slip down.  
Note: The utilization of fans will increase the  
air flow around the firebox. However, only a  
minimal increase in heat output should be  
anticipated.  
Step3. Centerouter-lockingsectionoverouter  
chimneypipe.Pushdownuntillockingjointhas  
firmly engaged.  
*Part of Offset/Return Package Model FTF8-ES30  
Step 4. Pull up slightly on return elbow to  
ensure locking joint has firmly engaged.  
Figure 40  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
14  
 
POWER TO THE FIREPLACE  
The Optional Blower Kit  
Operates on 115 volt 60 Hz  
150 watts AC  
After completing the installation of the optional  
combustion air vent system the actuator arm  
must be put in service and tested to ensure  
proper operation before completing any enclo-  
sure around the firebox. Failure to do so may  
result in extensive and costly rework.  
Note: Using a soapy water solution (50% dish  
soap, 50% water) is an effective leak test  
solution but it is not recommended, because  
the soap residue that is left on the pipes/  
fittingscanresultincorrosionovertime. Never  
use an open flame to check for leaks.  
HOUSE  
WIRING  
This provision is intended for connection to a  
decorative gas appliance incorporating an au-  
tomaticshut-offdeviceandcomplyingwiththe  
Standard for Decorative Gas Appliances for  
installation in vented fireplaces, ANSI Z21.60  
(1991) or American Gas Association draft re-  
quirementsforGas-FiredLogLightersforWood  
Burning Fireplaces, Draft No. 4 dated August,  
1993. Install in accordance with the National  
Fuel Gas Code, ANSI Z223.1. This complies  
with the revised U.L. 127 standard.  
Locate the actuator arm along the right side of  
the appliance firebox opening and refer to  
Figure 44.  
GROUND  
WIRE  
COVER PLATE  
Replace Cover Plate  
After Electrical  
Hook-Up  
House Wiring Must Be Secured  
With The Appropriate Electrical  
Connector To The Fireplace  
Convenience Outlet Wiring  
Figure 42  
Combustion  
Air Actuator  
THIS FIREPLACE IS NOT INTENDED TO BE  
USED AS A SUBSTITUTE FOR A FURNACE TO  
HEAT AN ENTIRE HOME. USE FOR SUPPLE-  
MENTARY HEATING ONLY.  
Vent Free Appliances  
This unit has been tested and approved to  
ANSI/IAS/AGAZ21.11.2forusewithunvented  
gas appliances and complies with the stan-  
dardforFactory-Builtfireplaces,UL127,when  
installed with unvented gas log sets. Special  
instructions with regards to mantle installa-  
tions must be taken into consideration when  
installing such appliances.  
Pull Forward to Open,  
Push Back to Close  
Figure 44  
The unit has been tested for use with any  
unvented log sets having a maximum rating of  
32,000 BTU. The minimum mantle configura-  
tion for these log sets are outlined inFigure 46.  
To operate, push the end of the actuator to the  
left as shown in Figure 44, until it "pops" free of  
its "locked" position. Pull the actuator forward  
to open the combustion air door, and push it  
backtoclose. To"lock"thecombustionairdoor  
closed, ensure the actuator is pushed all the  
way back then push the end of the actuators to  
the right until the step in the actuator moves  
behind the appliance front face within the slot-  
ted opening.  
BLOWER THREE  
PRONGED PLUG TO  
GROUNDED OUTLET  
Log sets with 40,000 BTU may be installed  
provided that no combustible mantle projec-  
tions are placed lower than 18 inches from the  
fireplace opening.  
Figure 43  
These fireplaces have been marked with a  
maximum rating of 32,000 BTU to assure that  
homeowners do not exceed the allowable lim-  
itsforallallowedinstallationsofmantles. That  
limit may be increased to 40,000 BTU, pro-  
vided that the mantle installed complies with  
the 18-inch limitation and a copy of these  
instructions are available.  
The FBK-100/200 Blower Kits are design certi-  
fied by Warnock Hersey for use with these  
appliances.  
Operate the actuator through several cycles  
including the "lock position. Ensuring proper  
operation and freedom of movement. Return  
the actuator arm to the locked position.  
Always check local building codes. Installation  
of the FBK Blower Kits must comply with local  
regulations as well as the National Electric  
Code.  
Gas Line Connection  
NEVER INSTALL AN UNVENTED GAS LOG  
SET WITH A BTU GREATER THAN 32,000 IF  
COMBUSTIBLE MANTLE PROJECTIONS ARE  
LOWER THAN 18 INCHES ABOVE THE FIRE-  
PLACE OPENING.  
Combustion Air Kits  
Install a 1/2" gas supply line through fireplace  
wall for connection to a decorative gas appli-  
anceinsidethefirebox. Outside,thegassupply  
line connects to a gas shut-off valve recessed  
flush into the wall or floor. The valve should be  
controlled by a removable valve key for safety.  
These appliances are equipped with an outside  
(make-up) air door and integral actuator arm. If  
theapplianceistobeinstalledwithanoutsideair  
vent system, use only FireCraft Models FAOK-4  
or FAOK-4LD Combustion Air Kits. These kits  
comecompletewithdetailedinstallationinstruc-  
tions and all components necessary in complet-  
ing a combustion air vent system.  
CAUTION: WHEN USING THE DECORATIVE  
GAS APPLIANCE, THE FIREPLACE DAMPER  
MUSTBESETINTHEFULLYOPENPOSITION.  
Always plumb gas line installation per local  
codes. Check all connections and test for gas  
leaks, using a gas leak test solution (also  
referred to as bubble leak solution).  
CAUTION:PLUMBINGCONNECTIONSSHOULD  
ONLY BE PERFORMED BY A QUALIFIED, LI-  
CENSEDPLUMBER. MAINGASSUPPLYMUST  
BE OFF WHEN PLUMBING GAS LINE TO FIRE-  
PLACE OR PERFORMING SERVICE.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
15  
 
If you’re installing a gas line, connect it before  
the fireplace is framed and enclosed in the  
finished wall. The gas knockout is determined  
by the indentation located at the bottom and  
slightly off center in the side refractories. THE  
KNOCKOUT IS ALWAYS REMOVED FROM IN-  
SIDE THE FIREPLACE. DO NOT REMOVE THE  
KNOCKOUT UNLESS YOU ARE INSTALLING A  
GAS LINE. If removal is attempted from the  
outer wrapper, side refractory damage may  
occur. With a medium-sized hammer, lightly  
tap the surface of the indentation. The refrac-  
torymaterialisverythininthisareaandiseasily  
removed. Once a small hole has been made,  
continue tapping until you have reached suffi-  
cientdiameterforthegaslinetofitthrough.The  
entire knockout does not have to be removed.  
Remove insulation in the gas line channel.  
It is especially important to insulate between  
the studs of an outside chase cavity and under  
the floor if the floor is above ground level. Do  
not place insulation directly against the fire-  
place or chimney system.  
Finished Wallboard  
Header  
12"  
Max.  
1 1/2"  
FIREPLACE FINISHES  
Mantels and Trim  
Combustible  
Mantel  
and Trim  
12"*  
Spacer  
Min.  
It is sometimes best to frame your fireplace  
after it is positioned and the chimney is in-  
stalled. Frame enclosure for chimney and fire-  
place with 2 x 4’s (or heavier) lumber.  
9"*  
Note:Theheadermayrestonthetwo(2)metal  
top spacers on top of the unit but the header  
must not be notched to fit around the spacers.  
Fireplace  
Opening  
*Both Of These Dimensions Must Be At Least 18”  
When An Unvented Gas Log Set Rated At 32,000  
BTU Or Higher Is Used. (Maximum 40,000 BTU)  
IMPORTANT:REPACKINSULATIONMATERIAL  
IN SQUARE HOLE AROUND GAS LINE, INTE-  
RIORANDEXTERIOROFFIREPLACE, TOSEAL.  
Thesefireplacesmaysitdirectlyonacombus-  
tible surface. A 2" air space is required be-  
tween combustible framing and the chimney.  
A1"airspaceisrequiredbetweencombustible  
framing and fireplace outer wrapper.  
Typical US Installation  
Figure 46  
Glass Doors  
If glass doors are to be installed on these  
fireplaces, refer to specific installation instruc-  
tions packed with the glass doors. Use only the  
doors that are listed for use with these fire-  
places. Use of other non-listed glass door on  
these fireplaces may constitute a potential fire  
hazard and is not recommended.  
Hearth Extensions and Wall Shields  
In Canada, the minimum height for a com-  
bustible mantel is 18" (457 mm) above the  
fireplace opening. Figure 45 shows typical  
Canadianinstallations. Forinstallationsother  
than Canada, combustible mantels and trim  
maybeinstalled12"abovethefireplaceopen-  
ing as per NFPA 211, Section 7-2.3.3. and  
Figure 46. If a mantel is of a noncombustible  
material, it is exempt from these require-  
ments as long as it does not interfere with the  
installation or operation of glass doors.  
A hearth extension must be installed with  
all fireplaces. It is to protect the combustible  
floor in front of the fireplace from both radiant  
heat and sparks. The hearth extension must  
extend 8" beyond both sides of the fireplace  
opening and 16" beyond the front (see Figure  
47 ). Use a hearth extension constructed of a  
durable noncombustible material having an  
equal or better (lower kvalue) insulatingvalue  
CAUTION: CERTAIN GLASS DOORS OVERLAP  
THE BLACK METAL FACING OF THE FIRE-  
PLACE. IF THE FIREPLACE HAS BEEN FACED  
WITHNONCOMBUSTIBLEMATERIALS, THERE  
MIGHT NOT BE SUFFICIENT CLEARANCE TO  
INSTALL THE GLASS DOORS OF YOUR  
CHOICE. ENSURE ADEQUATE CLEARANCE IS  
MAINTAINED AT ALL TIMES SO AS NOT TO  
INTERFERE WITH THE INSTALLATION AND  
OPERATION OF GLASS DOORS.  
2
of k = .43 BTU IN/FT HR °F or a thermal  
resistance that equals or exceeds r = 2.33 HR  
°F FT2/BTU IN. With these values, determine  
the minimum thickness/material required us-  
ing the formula and Page 17.  
Finished  
Wallboard  
Header  
8" Max.  
(203mm)  
Note: Any noncombustible material whose k  
value is less than .43 or whose r value is more  
than 2.33 is acceptable.  
COLD CLIMATE INSULATION  
If you live in a cold climate, it is especially  
importanttosealallcracksaroundthefireplace  
opening with noncombustible material and  
wherever cold air could enter the room. Sur-  
rounding materials must be caulked where it  
meets the black metal facing of the fireplace to  
avoid cold air intrusion. Use noncombustible  
caulking material only on fireplace facing to  
seal. Also, the outside air inlet duct should be  
wrapped with noncombustible insulation to  
minimize the formation of condensation. Do  
not place insulation materials on top of fire-  
place or against chimney sections.  
Combustible  
Mantel  
If the fireplace is installed on a combustible  
floor, use the metal safety strips (provided)  
on the floor extending half under the fire-  
place and half under the hearth extension  
(refer to Figures 6 & 7).  
Spacer  
18" Min.  
(457mm)  
A wall shield is required where a continuous  
perpendicular side wall is within 12" of the  
fireplace opening (Figure 48 ). Use a 36" W x  
36" H wall shield constructed of a durable,  
noncombustible material having an equal or  
better (lower k value) insulating value than k =  
Fireplace  
Opening  
Typical Canadian Installation  
Figure 45  
2
.54 BTU IN/FT HR °F. At no time may a  
perpendicular side wall be located closer  
Note: A 2" air space must be preserved for all  
combustible materials extending for any con-  
tinuous length adjacent to the chimney.  
than 9" from the fireplace opening.  
If fireplace is installed diagonally across a 90°  
corner; no wall shields are required.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
16  
 
Hearth Extension Dimensions  
A
B
C
D
16"  
38"  
8"  
54"  
C
C
B
D
Note: To convert inches to millimeters  
divide by 0.03937  
A
Figure 47  
Answer - The minimum required thickness of the Micore 160 is .875” ,  
therefore round up to 7/8” and use the nearest standard thickness available  
which is 1” .  
Methods of Determining Hearth Extension and Wall Shield  
Equivalents - To determine the thickness required for the alternate  
material when either the “ k” value or “ r” value is known, use either the  
k formula or r formula.  
Listed Material  
Example: If Micore 160 is to be used for the hearth extension fireplace,  
k (per inch) r (per inch)  
Listed Min.Thickness  
how thick must this material be?  
0.43  
Listed Material  
2.33  
1
T
"
L
KL  
rL  
kM = k value per inch of alternate material  
rM = r value per inch of alternate material  
TM = minimum thickness required for alternate material  
** Approved Alternate Materials for Floor/Hearth Protection  
AlternativeMaterials  
Thermal Values  
MinimumThickness  
(rounded to nearest 1/8 inch)  
T = standard thickness of the alternate material  
S
k (per inch) r (per inch)  
Min. Thickness  
KM  
rM  
TM  
kL = k value per inch of listed material  
rL = r value per inch of listed material  
Kaowool M Board  
.47  
.35  
2.13  
2.86  
1.09" (1-1/8")  
.81" (7/8")  
Micore 160™  
U.S. Gypsum  
T = minimum thickness of listed material  
L
1.07" (1-1/8")  
4.47" (4-1/2")  
Micore 300™  
U.S. Gypsum  
.46  
2.17  
.52  
Note: An asterix “*” indicates, it is a value taken from Table 1.  
Using the k formula:  
Durock™ Cement Board  
U.S. Gypsum  
1.92  
Minimum  
thickness of  
alternate  
k-value (per Inch) of  
alternate material (kM) x  
k-value (per inch)  
Specified min.  
thickness  
of listed  
=
Hardibacker™  
1.95  
2.30  
2.82  
.513  
.435  
.355  
4.53" (4-1/2")  
5.35" (5-3/8")  
6.56" (6-1/2")  
Hardibacker 500™  
material (TM)  
of listed material (kM)  
material (T )  
L
Cultered Stone Hearth-  
stone™  
TM (inches)  
TM (inches)  
=
=
kM  
*.43  
x
T
L
Wonderboard  
3.23  
.61  
.31  
7.51" (7-1/2")  
1.42" (1-3/8")  
Super Firetemp M  
Johns-Manville  
1.64  
*.35  
*.43  
x
x
1"  
1"  
1.26" (1-1/4")  
Super Firetemp L  
Johns-Manville  
.54  
1.85  
Face brick  
9.00  
5.00  
5.00  
12.5  
11.0  
.111  
.20  
.20  
.08  
.09  
20.93" (20-7/8")  
11.63" (11-5/8")  
11.63" (11-5/8")  
29.07" (29-1/8")  
25.58" (25-5/8")  
.875 (inches) =  
.875  
Common brick  
Cement mortar  
Ceramic tile  
Marble  
Answer - The minimum required thickness of the Micore 160 is .875,  
therefore round up to 7/8” and use the nearest standard thickness  
available which is 1.  
Using the r formula:  
Table 1  
Minimum  
thickness of  
alternate  
material  
r-value (per Inch)  
of listed material  
r-value (per inch)  
of alternate material  
Specified min.  
thickness  
of listed  
** If the hearth extension material(s) that is intended to be used is NOT listed  
on Table 1, the material can still be used if the material(s) is noncombustible.  
However, the manufacturer of the material must provide either the listed k-  
value per inch or r-value per inch with listed thickness so that the minimum  
thickness required for the hearth can be calculated (per instructions on this  
Page and/or as specified in the NFI Certification manuals).  
=
x
material  
TM (inches)  
TM (inches)  
=
=
rL  
rM  
x
x
x
T
L
Note:AlsoseeNFI(National FireplaceInstitute)CertificationManualsshowing  
other acceptable calculation methods and acceptable alternate materials  
which can be used.  
*2.33  
*2.86  
1"  
1"  
.875 (inches) =  
.875  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
17  
 
The sum of all R values” is: .70 + .10 +. 038  
+ .10 = .938  
Wall Shield Required  
Where Less Than 12"  
ThiswouldNOTbeanacceptablecombination  
of material for the hearth extension since the  
totalcalculated“Rvalue” ofthematerialsused  
is under the required R value” of 2.33. An  
additional layer of insulating materials must  
be used.  
36"  
5 1/2"  
36"  
Note: Also see NFI Certification Manuals for  
expanded explanation on calculating R val-  
ues” when multiple materials are used.  
2"  
C
Max. Thickness Of Hearth Extension When  
Circulating Models Are On The Floor  
B
D
C
A
WARNING: THE CRACK BETWEEN THE  
FIREPLACE AND THE HEARTH EXTEN-  
SION MUST BE SEALED WITH A NON-  
COMBUSTIBLE MATERIAL.  
Figure 50  
Figure 48  
Secure the hearth extension to the floor to  
prevent possible shifting.  
Calculating Minimum Thickness if Multiple  
Materials are Used  
FINISH TO YOUR TASTE  
WARNING: WHEN INSTALLING HEARTH  
EXTENSION IN FRONT OF A NON-CIRCU-  
LATING FIREPLACE MODEL, THE FIRE-  
PLACE MUST BE RAISED IF HEIGHT OF  
HEARTH EXTENSION EXCEEDS 7" ABOVE  
THEBOTTOMOFFIREPLACE(FIGURE49).  
At times it is important to know what  
combination of materials are acceptable for  
use as floor protection. The R values” are  
usedtodetermineacceptablecombinationsof  
materialsbecauseRvalues” areadditivewhere  
r and k values are not.  
There are a wide variety of finished looks” for  
these fireplaces, from formal wall decor with  
elaborate mantels to rustic wood paneling or  
warm brick facings.  
Only noncombustible materials like stone, tile,  
brick, etc., may overlap the black front facing.  
Donotextendthesematerialsbeyondtheblack  
facing and into the firebox area. Be sure not to  
interfere with the installation and operation of  
glass doors or block the upper or lower grilles.  
Sealalljointsbetweentheblackfacingandwall  
surrounds to prevent air intrusion. Use non-  
combustible caulking material only to seal the  
black metal facing to the surround material on  
the finished wall.  
“ Rvalue” = 1/k = “ r” xthicknessofmaterial  
used  
Example: Given that the required R value”  
for a suitable floor protector used must be  
equal to or greater than:  
R” = rL x T = 2.33 x 1” = 2.33.”  
L
7 1/2"  
If it is desired to elevate a marble hearth ex-  
tension to a level of 5” or more above the floor  
surface. What combination of noncombus-  
tible materials can be used to accomplish this?  
Max. Thickness Of Hearth Extension When  
Non-Circulating Models Are On The Floor  
Combustible materials may project beyond the  
sides of the fireplace opening as long as they  
are kept within the shaded areas illustrated in  
Figure 51.  
Figure 49  
If common brick is used so that the 3 1/2”  
dimension is the height, Rfor the common  
brick becomes:  
WARNING: WHEN INSTALLING THE  
HEARTH EXTENSION BE CAREFUL NOT  
TO BLOCK THE HEAT-CIRCULATING AIR  
INLETGRILLONCIRCULATINGMODELS.  
Combustible  
Materials  
brick  
Fireplace  
Allowed In  
RM = rM x TS = 0.20 x 3 1/2" = .70  
Shaded Area  
Safe Zone”  
1"  
Using 1/2” of mortar to set the brick, Rfor  
the mortar is calculated as follows:  
mortar  
45°  
WARNING: WHEN INSTALLING HEARTH  
EXTENSION IN FRONT OF A CIRCULAT-  
INGFIREPLACEMODEL, THEFIREPLACE  
MUST BE RAISED IF HEIGHT OF HEARTH  
EXTENSIONEXCEEDS2"ABOVEBOTTOM  
OF FIREPLACE (FIGURE 50 ).  
12"  
RM = rM x TS = 0.20 x 1/2" = .10  
Min. Distance To  
Unprotected Side Wall  
Next, a 3/4" marble slab set in 1/2" mortar cov-  
ers the brick, “Rfor the marble and mortar  
becomes:  
12"  
Figure 51  
marble  
RM = rM x TS = 0.05 x 3/4" = .038  
mortar  
RM = rM x TS = 0.20 x 1/2" = .10  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
18  
 
INSTALLATION COMPONENTS  
The following items are available for use in the  
installation of this appliance.  
(FBK-200 Models Only)  
Chimney Section  
63L10  
63L13  
63L14  
63L15  
62L92  
62L93  
FTF8-12  
FTF8-18  
FTF8-36  
FTF8-48  
FTF8-18C  
FTF8-36C  
Forced Air Blower Kits  
-Single Speed  
-Variable Speed  
80L84  
80L85  
FBK-100  
FBK-200  
Canadian  
Chimney Section  
Firestop Spacer (30°)  
63L32  
F8FS30-2  
63L38  
63L39  
F8F6  
F8F12  
Flashing  
Offset/ Return  
Package (30°)  
63L22  
FTF8-ES30  
Outside Combustion Air Kits  
(with duct)  
(without duct)  
81L87  
81L88  
FOAK  
FOAK-LD  
Stabilizer  
63L25  
FTF8-S4  
Chase Termination  
96L20  
FTF8-CTT  
Combination  
Offset/Return Elbow  
63L28  
FTF8-OR15  
Firestop Spacer (Flat)  
63L31  
F8FS-2  
Round Termination  
63L42  
FTF8-CTD  
Storm Collar  
63L59  
FSC  
Chase Termination  
96L22  
FTF8-ATT  
Locking Band  
63L60  
FLB  
Shipping Weight  
188 lbs.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
19  
 
INSTALLATION COMPONENTS  
(Not Provided)  
Chase Termination  
(Square)  
63L51  
FTF8-CT2  
Attic Shield Assembly  
63L67  
FTF8-FSAS  
Chase Termination  
(Square)  
Chase Termination  
(Round)  
63L48  
FTF8-CT1  
Cold Climate Kit  
H7412  
CCK-HCRD  
63L45  
FTF8-CTDT  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products.  
Consult your local distributor for fireplace code information.  
Printed in U.S.A. © 2007 by LENNOX HEARTH PRODUCTS  
1110 West Taft Avenue  
P/N 850,047M REV. A 12/2008  
Orange, CA 92865  
 

KWC Indoor Furnishings 10031991 User Manual
Lenovo SONAR 9227 HB2 User Manual
LG Electronics Bluetooth Headset HBM 520 User Manual
LG Electronics DVR STB 2000 User Manual
Lincoln Electric Welder IM10078 User Manual
Logitech Speaker System 575HSD User Manual
Lux Products Thermostat PSDFC150 User Manual
Magnadyne Computer Monitor MV750G Gray User Manual
Maxtor Computer Drive 96147H6 User Manual
Meade Telescope LX50 User Manual